a. Two area samples outside the work area in uncontaminated areas of the
building, remote from the decontamination facilities.
b. Primary location selection shall be within 10 feet of isolation barriers.
c. Where negative ventilation exhaust runs through uncontaminated building
areas, one of the area samples will be required in these areas to monitor
any potential fiber release.
d. Where adjacent non-work areas do not exist, an exterior area sample shall
be taken.
e. One area sample within the uncontaminated entrance to each
decontamination enclosure system.
f. One area sample within 5 feet of the unobstructed exhaust from each AFD
exhausting indoors.
2. Projects Solely Employing Glove-Bag and/or Tent Procedures:
3. One Baseline sample shall be taken near each entrance to the Work Area.
4. Area air samples shall be taken daily no less than 10 feet nor more than 15 feet
from the glove-bag(s) or tent(s) actively being used in the abatement, or a similar
appropriate and representative distance, using the following guidelines:
G. Glove-Bag Removals:
1. For projects involving more than 25 linear feet and less than 260 linear feet, a
minimum of two samples (one baseline and one active abatement area sample)
shall be taken in each homogeneous Work Area.
2. For projects involving 260 linear feet or more and less than 500 linear feet of
insulation to be removed, a minimum of two samples shall be taken concurrently
with the abatement.
3. For projects involving 500 linear feet or greater of insulation to be removed, a
minimum of three samples shall be taken concurrently with the abatement, for
each 1,000 liner feet of removal.
H. Tent Procedures:
1. For projects involving more than 25 linear feet or 10 square feet, a minimum of
three continuous samples shall be taken concurrently throughout abatement.
I. Post-abatement clearance air monitoring for projects not solely employing glove-bag
procedures shall include a minimum number of area samples inside each homogeneous
work area and outside each homogeneous work area (five samples inside/5 samples