SECTION 02082
section Clearance Testing of Work Areas in this Specification.
B. For TEM analysis, the clearance monitoring will be considered satisfactory if conducted in
accordance with 40 CFR Part 763, Subpart E, Appendix A - Section IV - Mandatory
C. Interpretation of Transmission Electron Microscopy Results to Determine Completion of
Response Actions.
1.29 LOCKDOWN ENCAPSULATION PROCEDURES
The following procedures shall be followed to seal in nonvisible residue while conducting
lockdown encapsulation on all surfaces from which ACM removed:
a. Only encapsulants rated as acceptable or marginally acceptable on the basis of Battelle
Columbus Laboratory test procedures and rating requirements developed under the 1978
USEPA Contract shall be used for lockdown encapsulation.
b. The encapsulant solvent or vehicle shall not contain a volatile hydrocarbon unless
reviewed and approved by DEP.
c. Latex paint with solids content greater than 15 percent shall be considered a lockdown
sealant for coating all non-metallic surfaces.
d. Encapsulants shall be applied using airless spray equipment. Spraying is to occur at the
lowest pressure range possible to minimize fiber release from encapsulant impact at the
surface. It shall be applied with a consistent horizontal or vertical motion.
1.30 CLEARANCE TESTING OF WORK AREAS
A, Clearance Procedure for Areas Prepared Utilizing Full Containment Enclosure:
1. Clearance Procedure for Areas Prepared Utilizing Full Enclosure:
a) Cleaning of the work areas and other contaminated areas shall be conducted in
accordance with procedure described below:
Step 1. Clean-up Visual Inspection
Step 2. Final Visual Inspection and fiber reoccupancy clearance count of <0.01
fiber/cc of air using NIOSH Method 7400 and less than 70 structures per
mm^ when using Transmission Electron Microscopy.
b) Area air samples will be collected prior, during and after abatement according to
established air clearance criteria per New York City Title 15.
c) To determine final air clearance reoccupancy, the following air samples shall be
02082-43
CITY_21 MCI 00_014563816
NYC-WTC_000454616