SECTION 02082
industrial hygiene laboratory representative for approval.
J. Air monitoring and inspection shall be conducted by the Contractor's competent person.
K. Continuous (daily or per shift) monitoring and inspection will include Work Area samples,
personnel samples from the breathing zone of a worker to accurately determine the employees'
8-hour TWA (unless Type C respirators are used) and decontamination unit clean room samples.
L. Work Area samples and employee personnel samples shall be taken using pumps whose flow
rates can be determined to an accuracy of +5-percent, at a minimum of two liters per minute.
This must be demonstrated at the job site.
M. Sampling and analysis methods shall be per NIOSH 7400A.
N. Test Reports:
1. Promptly process and distribute one copy of the test results, to the Commissioner.
9 Prompt reports are necessary so that if required, modifications to work methods and/or
practices may be implemented as soon as possible.
3. Contractor shall by facsimiley-and notify the Commissioner with 24 hours of the results of
each test, followed by written notification within three days.
4. Competent person shall conduct inspections and provide written reports daily.
Inspections will include checking the standard operating procedures, engineering control
systems, respiratory protection and decontamination systems, packaging and disposal of
asbestos waste, and any other aspects of the project which may effect the health and
safety of the people and environment.
O. All costs for required air monitoring by the Contractor's competent person shall be borne by
Contractor.
P. The City reserves the right to conduct air and surface dust sampling in conjunction with and
separate from the Testing Laboratory for the purposes of Quality Assurance.
Q. All samples shall be accompanied by a Chain of Custody Record that shall be submitted to the
Resident Engineer upon completion of analysis.
1.28 WORK AREA CLEARANCE LEVELS
"Clearance Air Monitoring" shall mean the employment of aggressive sampling techniques with
a volume of air collected to determine the airborne concentration of residual fibers, and shall be
performed as the final abatement activity.
A. Clearance and/or Reoccupancy Criteria:
The clearance criteria shall be applied to each homogeneous Work Area independently as per
02082-42
CITY_21 MCI 00_014563815