SECTION 02082
A. Air Sampling and Analysis:
Section 763.90 of AHERA and the New York State Education Department requires that public
schools accomplish final air sampling and analysis of all removal, encapsulation, or enclosure
projects by using the transmission electron microscopy (TEM) method. Under AHERA,
nonpublic schools must also use TEM for final air analysis. Note that no final air clearance is
required for small-scale, short-duration O & M projects, unless there is a break in the
containment.
B. The TEM Method for Final Air Clearance:
The TEM method involves the collection of at least five samples inside the work area, five
samples representative of ah’ outside of the work area collected at the same time as the indoor
samples, and three quality control samples. The air samples must be collected using
“aggressive” methods of artificially disturbing the air in the work are before sampling, as
described in Appendix A, Section III (B)(7)(d) of the AHERA Rule. The volume of air drawn
for each of the five samples collected within the functional space must be equal to or greater than
1,199 L of air for a 25mm filter or equal to or greater than 2,799L of air for a 37mm filter. If the
average result of the five samples collected inside the work area meets an average of 70
structures per square millimeter (70s/mm ’ ). the response action is considered complete.
The response action may also be considered complete when the average concentration of
asbestos of the five air samples collected within the affected work area and analyzed by the TEM
method is not statistically significantly different, as determined by the Z-test calculation
described in Appendix A of AHERA, from the average asbestos concentration of five air
samples collected outside the affected work area and analyzed in the same manner, and the
average asbestos concentration of the three quality control samples is below 70s/ninr. the test is
voided and resampling must be done. If the difference in average asbestos concentration
between in and out samples is statistically significant, the contractor must reclean the work area
and resampling must be done at the Contractor’s expense.
C. PCM Air Monitoring:
The phase contrast microscopy (PCM) method involves collecting at least five samples inside the
work area by aggressive methods as described in Appendix A, Section III (B)(7)(d) of the
AHERA Rule and having them analyzed on a PCM microscope. Unlike the TEM method, the
PCM method does not call for the samples to be averaged; each sample stands on its own.
The clearance standard for PCM is 0.01 fibers per cubic centimeter of air (0.01 f/cc). If all five
samples pass this standard, the response action is considered complete. If even one sample fails
to pass the standard, the Contractor must reclean the area and resampling must be done.
1.27 TESTING LABORATORY SERVICES
A. "Air Sampling" shall mean the process of measuring the fiber content of a known volume of air
collected during a specific period of time. The procedure utilized for asbestos follows the
NIOSH Standard Analytical Method 7400 or the provisional transmission electron microscopy