NYC 9/11 Public Portal Document
Part V - Quality Assurance Project Plan
133-135 Greenwich Street/21-23 Thames Street
Airtek Project 05-0701 - Rev 1 - February 1, 2006
More detailed information is available from individual SOPs for the test of interest or the
published method.
Table 10-1
RCRA Waste Characterization Analytical Method, Container, Preservation and Holding
Times for selected aqueous and non-aqueous matrices.
Min Conta/ner Sample Holding
Ana/yte Method volume Type Preservatio Time
(mL) n
Acidity EPA 305.1/SM 2310B 1000 P,G Cool, 4 °C 14 days
Alkalinity EPA 310.1/SM 2320 B 1000 P,G Cool, 4 "C 14 days
Chlorinated EPA 608/ SW 8080 1000 GA Cool, 4 “C 7/14
Pesticides and days
PCB’s
Corrosivity SW846 Method 9045D or 9040C 500 P,G, Cool, 4 “C immed
Flame AA Metals SW 7000/ 500 P HNO3 pH<2 6 mo
GFAA Metals SW 7000/ 500 P HNO3 pH<2 6 mo
Hexavalent SW7186 500 P, G Cool, 4 “C 24 hr
Chromium
ICP Metals SW 846 Method 601 OB or 6020 500 p HNO3 pH<2 6 mo
Ignitability ASTM D-93-79 or D-93-80 100 g G Cool, 4 "C 28 days
(Flashpoint) orD-3278-78.
Mercury EPA 245.1/SM3112 B/ 500 P HNO3 pH<2 6 mo
SW846 Method 7470A
PAH SW 8100____________ 1000 GA Cool, 4 “C 7/40days
PAH SW 8310 1000 GA Cool, 4 “C 7/30
days
PCB EPA 608/ SW 8082 1000 GA Cool, 4 “C 7/40
days
pH EPA 150.1/SW 9040 B/ 500 P,G Cool, 4 “C immed
Reactive Cyanide SW 9012 A, 7.3 1000 P,G Cool, 4 “C 14 days
Reactive Sulfide SW 9030 B/ 9034 500 P,G zinc acetate, 7 days
NaOH pH>9
TCEP Semivolatile EPA 625/ SW 3510 C/ 8270C 1000 GA Cool, 4 “C 7/40
Organics days
TCEP Volatile EPASW846-1311/8260B 1000 GA Cool, 4 “C 7/40
Organics days
TCEP Pesticide SW846 Method 8081A 1000 GA Cool, 4 “C 7/40
days
TCEP Herbicide SW846 Method 8151A 1000 GA Cool, 4 “C 7/40
days
P = plastic, HDPE G = glass GA= amber glass VOA = 40 mL vial
Preservation should be performed at time of sample collection. Sample bottles with or without preservative
may be obtained by contacting the laboratory. Indication of preservative would be helpful either on the
label or a sample chain of custody (also available from the laboratory). The holding times listed in the table
are the maximum allowable time a sample can be held before analysis and still be in compliance with the
EPA regulations. Sample collection date and time are needed to ensure that holding times are met properly.
69