NYC 9/11 Public Portal Document
Part V - Quality Assurance Project Plan
133-135 Greenwich Street/21-23 Thames Street
Airtek Project 05-0701 - Rev 1 - February 1, 2006
values and identification of flags indicating any anomalies are recovered by the operator
by downloading a sample summary to a laptop or handheld computer.
10.2.10.2 Continuous Monitoring 0/PM2.5 via Met One E-BAM Samplers
The monitors selected to continuously measure PM2.5 are beta-attenuation monitors
manufactured by Met One Instruments, Inc. (Met One). The E-BAM monitors will be
equipped with particle size selective inlets. The design of the inlets is such that particles
larger than the desired size range will be removed from the air flow at the prescribed air
flow rate. The units will be equipped with an inlet head to separate PM2.5. Sampling flow
rate is critical to maintain the proper particle size cut points of the inlets. Flow rates are
maintained at 16.7 liters per minute in the E-BAM monitors using an integral flow meter,
pressure sensor, and ambient temperature sensor on board each monitor.
10.2.11 RCRA Waste Sampling
Bulk sample collection of building components for hazard classification will include the
following RCRA waste characteristic analytical procedures:
• Ignitability (RCRA waste code DOOl). American Society of Testing Materials
(ASTM) method D-93-79 or D-93-80 or D-3278-78.
• Corrosivity (RCRA waste code D002). Method 9045D or 9040C in “Test
Methods for Evaluating Solid Waste, Physical/Chemical Methods,” EPA
Publication SW-846. NOTE: liquids may be characterized as corrosive wastes.
• Reactivity (RCRA waste code D003). Analytical methods outlined in sections
7.3.3.2 or 7.3.4.2 of “Test Methods for Evaluating Solid Waste,
Physical/Chemical Methods,” EPA Publication SW-846.
• Toxicity. The characteristics of toxicity carry the RCRA waste codes of D004
through D043. Each waste code identifies the specific chemical component for
which the waste is classified as toxic. The samples to be analyzed for the
characteristic of toxicity must be prepared using the Toxicity Characteristic
Eeaching Procedures (TCEP) per Method 1311 in “Test Methods for Evaluating
Solid Waste, Physical/Chemical Methods,” EPA Publication SW-846. The
analytical method applied to the resulting leachate depends on the type of
chemical being analyzed for, as follows:
1. Mercury (D009) Method 7470A (aqueous samples) of “Methods for
Evaluating Solid Waste, Physical/Chemical Methods,” EPA Publication
SW-846Metals/inorganics other than mercury. Method 6010B or 6020
of “ Methods for Evaluating Solid Waste, Physical/Chemical Methods,”
EPA Publication SW-846.
2. TCEP volatile organic compound (VOC) toxic constituents. Method
SW846-1311 Method 8260B;
3. TCEP semivolatile organic compound (SVOC) toxic constituents, SW846-
66