Thanks gentlemen.
George: Is it true to say that only the sixth floor library was
elevated above 1.5 ug/m3? The other elevated area samples that were
collected in July were collected during the cleaning of the
ventilators, just outside of the containment, but while the school
was unoccupied. All areas were re-cleaned and again agressively
sampled. The levels were then found to be below detection
(<1.5ug/m3).
>> "George - Taylor Env." <[email protected]> 10/02/02
» 12:15PM »>
10.2.02
Kelly R McKinney PE
Associate Commissioner, Environmental Health NYC Department of Health
and Mental Hygiene
125 Worth Street,Room 616
New York,NY 10013
Re: Stuyvesant High School
345 Chambers Street
New York, NY.
Dear Mr.McKinney
As requested please find enclosed summary of all work performed at
the aforementioned facility.
(7.13.02-8.31.02)
1.. Cleaning and Testing of Unit Ventilators Kiss Construction
Inc.(KCI) performed environmental cleaning of all wall and ceiling
mounted Unit Ventilators within the facility. This cleaning work was
performed within tent enclosures under negative pressure. Each Unit
Ventilator was visually inspected by Taylor Environmental
Group,Inc.(TEG) and if found to be free of visible dust/debris a wipe
sample was collected from the Unit Ventilator to be tested for lead.
If sample results indicated a lead concentration exceeding the NYC
Board of Education/NYC School Construction Authority ("NYC SCA")
clearance level of 20 ug/sq.ft.then the Unit Ventilator was
re-cleaned and re-tested.
Air Monitoring-