During the cleaning of the Unit Ventilators within each tent
enclosure, TEG performed personal (OSHA) air monitoring on KCI's
personnel working within each tent, in addition to ambient area
monitoring outside each tent. Personal and area samples were
analyzed for lead via NIOSH Method 7082, and the results of all
samples collected indicated airborne lead concentrations below the
current OSHA action level of 30 ug/m3.
2. HVAC System Wipe Sample Testing
At the conclusion of all HVAC/Duct cleaning (performed by the HVAC
Cleaning Contractor) on each floor, TEG collected wipe samples from
the return and supply ducts within each zone to be analyzed for lead
via EPA Method SW846-7420. ( Clearance level of 20 ug/sq.ft.)
In addition wipe samples to be analyzed for lead were collected from
the air handling units for HVAC systems one (1) through fifteen (15)
after they had been cleaned by the HVAC Cleaning Contractor. (
Clearance level of 20 ug/sq.ft.).
3. General Cleaning
At the conclusion of all Unit Ventilator and HVAC/Duct related
cleaning work on each floor of the facility, KCI performed general
cleaning in each functional space on the entire floor. At the
conclusion of the general cleaning a visual inspection was performed
by TEG and a representative from the NYC SCA. If the visual
inspection was successful then TEG collected two (2) wipe samples
from each functional space within that floor to be analyzed for lead
via EPA Method SW846-7420.( Clearance level of 20 ug/sq.ft.).
4. Final Clearance Air Monitoring
At the conclusion of all the aforementioned work performed on each
floor, final clearance air monitoring was conducted according to the
following table:
Sample Type
Analytical Methodology
Number of Samples Collected Per Floor
Airborne Asbestos
Transmission Electron Microscopy AHERA Protocol
10
Airborne Lead
NTOSH 7082
5
All final clearance air monitoring was performed using aggressive
techniques through the use of leaf-blowers and 20 " box fans. (
Airborne asbestos clearance level 70 as/mm2 , Airborne lead clearance
level 1.5 ug/m3 or below detection limit (bdl)).
5. Evaluation of Carpet Contamination and Testing
Tn the Auditorium, Library, Secretary's Office (Room 105),
Principal's Office and Conference Room, a procedure was performed to
evaluate the levels of airborne asbestos fibers that could result
from vacuuming the carpet using standard commercial vacuums. This
procedure was performed by KCI inside a tent enclosure whilst TEG
performed air monitoring. Air samples were collected inside and
outside of the tent enclosure (s) and were analyzed for airborne
asbestos (TEM AHERA Protocol) .
Auditorium and Secretary's Office (Room 105) Carpet Removal
CITY_21MC100_013074170
NYC-WTC_000433535