January 30, 2002
Mr. Eric Rappel
TDX-BECOM Joint Venture
25-34 Jackson Avenue
Long Island City, NY 11101
RE: 100 TRINITY PLACE, NEW YORK
NADCA VACUUM TEST
As instructed, we performed the NADCA VACUUM TEST on January 29, for
evaluating the cleanliness of non-porous HVAC component surfaces. Samples
were taken on the tenth, ninth, seventh, fifth and third floors.
All results were within the parameters of below 0.75mg/100 square cm.
acceptable level.
Attached is the Certificate of Analysis from Environmental Monitoring and
Consulting Associates.
Should you have any question, please do not hesitate to call.
Very truly^urs,
Mr. Marc Werkman- President (ASCS)
Attachincni; report
1V.X.IOOIKtNny.NAPl.AVA<TKST.IJ!3OO2 NADCA