Asbestos Abatement

i) Seal fixed objects with two individual layers, minimum, of 6-mil polyethylene sheeting.

j) Pre-clean entire Work Area utilizing using HEPA-vacuum and wet­ cleaning techniques. Methods of cleaning that raise dust, such as dry sweeping or use of vacuum equipment not equipped with HEPA-filters, is prohibited.

k) Install isolation barriers (i.e., sealing of all openings, including but not limited to windows, corridors, doorways, skylights, ducts, grills, diffusers, and other penetrations within the Work Area) using two layers of 6-mil polyethylene sheeting and duct-tape.

1) Construct rigid framework to support Work Area barriers.

(1) Framework shall be constructed using 2-inch by 4-inch wooden or metal studs placed 16 inch on center when existing walls and/or ceiling do not exist for all openings greater than 32 square feet. Framework is not required except where one dimension is one foot or less or the opening will be used as an emergency exit.

(2) Apply a solid construction material, minimum thickness of 3/8-inch to the Work Area side of the framing. In secure interior areas, not subject to access from the public or building occupants, an additional layer of 6-mil polyethylene sheeting may be substituted for the rigid construction material.

(3) Caulk all wall, floor, ceiling, and fixture joints to form a leaktight seal.

m) Seal floor drains, sumps, shower tubs, and other collection devices with two layers of 6-mil plastic and plywood, as necessary, and provide a system to collect all water used by the Contractor. Collected water shall be passed through a water filtration system prior to being discharged into the sanitary sewer.

n) Remove ceiling mounted objects not previously sealed that will interfere with removal operations. Mist object and surrounding ACM with amended water prior to removal to minimize fiber dispersal. Clean all moveable objects using HEPA-vacuum and wet-cleaning techniques prior to removal from the Work Area.

o) Fiberglass insulation with intact coverings shall be protected in place during abatement activities. These materials shall be CAPITAL PROJECT NUMBER PO79201K 02081-73 100: CONTRACT DOCUMENTS REV. May 3,2000 - 73 -100% CONTRACT DOCUMENTS REV. 0: DATE

CITY_21MC100_006631322

NYC-WTC_000416834

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000416834Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Asbestos sampling chain of custody form

NYC-WTC_000233286

Chain of custody form for asbestos samples referencing New York State Department of Labor regulations and sample tracking details.

Similar indexed content

Asbestos, NY DOL reference

NYC-WTC_000441450

Asbestos standards reference page from NY Department of Labor materials.

Similar indexed content

Compare copies and versions →