ATC IAQ measurements report for Stuyvesant High School dated January 2, 2002.
11 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗Indoor air quality report for Stuyvesant High School, January 2002.
NYC-WTC_000401739–000401742OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Teniperciliire
Indoor dry bulb temperature measurements ranged from .66.8 °F to 74.4 °F. Two (2) measurements were below the range of 68' to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These measurements were collected on the 4^1'’, 5’^1' and 6’^' ’ floors. The outdoor temperature range was 36.7 to 42.1 °F.
Rcicilive Hiimic/ilv
The relative humidity indoors ranged from 13.0 percent to 29.3 percent. All measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 16.5 and 19.9 percent;
Ccirhon Dioxic/e Concentratron
Carbon dioxide concentrations indoors ranged from 470 ppm to 1450 ppm. Nine (9) COg measurements were above the ASHRAE Standard -62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) COo concentrations were 459 ppm and 478 ppm. Therefore, the maximum.acceptable level of CO2 at this location was 1 178 ppm (background level + 700 ppm). The highest reading, 1450 ppm, was in Room 327. Rooms with COo levels above the recommended maximum were found on 4^1 and 7^1 floors. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concenlralion
Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was Ippm.
Rexpirab/e Parliciilates (PM2,
Respirable paniculate concentrations* indoors ranged between 5 pg/mJ to 20 pg/mA All measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations were 20 and 25 pg/mJ.
Filters with a higher efficiency rating were installed on the HVAC units that serve rooms on the 3''d, 4^1, 6^1 and 7tli floors (See Attachment 1). The PMgj concentration range for those rooms was 5-20 pg/m3 with an average of approximately 10 pg/m^. The PM2.5 concentration range for the other rooms was 6-19 pg/m-’ with an average of approximately 9 pg/m-’. The average Pl^2.5 concentration for the entire school building was approximately 9 pg/m^. In addition to higher efficiency rating Alters on their HVAC units, portable High Efficiency Particulate Air (HEPA) purifiers were placed in Rooms 327, 333, 638 and 740. The PM2.5 concentration range for these rooms was 5 - 25 pg/nP with an average of approximately 14 pg/m-’.
CITY_21MC100_002897694
NYC-WTC_000401741
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000401735
ATC IAQ measurements report for Stuyvesant High School dated January 2, 2002.
11 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311194
ATC report of indoor air quality measurements at Stuyvesant High School (M477).
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311190
ATC report on indoor air quality measurements at Stuyvesant High School (M477).
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000255777
ATC memo detailing IAQ measurements at Stuyvesant High School.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000401790
ATC reports IAQ measurements taken January 11, 2002 at Stuyvesant High School.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000273995
December 2001 IAQ measurements at Stuyvesant High School with BOE contact.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000401506
Indoor air quality measurements collected December 17, 2001 at Stuyvesant High School.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000401743
Indoor air quality measurements report for Stuyvesant High School, January 8, 2002.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000274045
December 20, 2001 IAQ measurements at Stuyvesant High School for BOE.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000273973
Memorandum regarding indoor air quality measurements at Stuyvesant High School.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000255518
IAQ measurements reported for Stuyvesant High School; December 10, 2001.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000255522
Indoor air quality measurements at Stuyvesant High School, December 12, 2001.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000401735
ATC IAQ measurements report for Stuyvesant High School dated January 2, 2002.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000401743
Indoor air quality measurements report for Stuyvesant High School, January 8, 2002.
Similarity score 0.992 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000255855
ATC memo/IAQ measurements reported for Stuyvesant High School.
Similarity score 0.992 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311198
ATC report of indoor air quality measurements at Stuyvesant High School (M477).
Similarity score 0.992 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311190
ATC report on indoor air quality measurements at Stuyvesant High School (M477).
Similarity score 0.992 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311194
ATC report of indoor air quality measurements at Stuyvesant High School (M477).
Similarity score 0.992 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000401735
ATC IAQ measurements report for Stuyvesant High School dated January 2, 2002.
Similar indexed content
NYC-WTC_000311194
ATC report of indoor air quality measurements at Stuyvesant High School (M477).
Similar indexed content
NYC-WTC_000311190
ATC report on indoor air quality measurements at Stuyvesant High School (M477).
Similar indexed content
NYC-WTC_000255777
ATC memo detailing IAQ measurements at Stuyvesant High School.
Similar indexed content
NYC-WTC_000401790
ATC reports IAQ measurements taken January 11, 2002 at Stuyvesant High School.
Similar indexed content