Indoor air quality report, Stuyvesant HS, Jan 2002

Machine-extracted title · confidence 42%

ATC report of indoor air quality measurements at Stuyvesant High School (M477).

NYC-WTC_000311198–000311201
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Temncrgliirc

Indoor dry bulb temperature measurements ranged from 69.0 °F to 75.4 °F. Only tw'o (2) measurements were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These measurement were collected from rooms 404 and 638. The outdoor temperature range was 32.0 to 34.3 °F.

Re/c/iive Hiiniic/ilv

The relative humidity indoors ranged from 12.7 percent to 27.7 percent. All measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 40.3 and 42.2 percent.

CciHjonDioxicfe Conccnirgnon

Carbon dioxide concentrations indoors ranged from 495 ppm to 1399 ppm. Four (4) CO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations were 402 ppm and 5 10 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1210 ppm (background level + 700 ppm). The highest reading, 1399 ppm, was in Room 503. Rooms with CO2 levels above the recommended maximum were found on 3'"'^, 4^11 and 5^1'* floors. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Ccii'hon Monaxide Conceiilration

Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations were below' the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 1 ppm.

Respirable Pciiiiciilxile.x (PM2,5)

Respirable particulate concentrations* indoors ranged between 5 pg/nP to 17 pg/nP. All measurements were below' the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations were 12 and 15 pg/m-’.

Filters with a higher efficiency rating were installed on the HVAC units that serve rooms on the 4'l\ 6^1^ and 7^^’ floors (See Attachment 1). The PM? 5 concentration range for those rooms was 5-17 pg/m^ with an average of approximately 10 pg/m^. The PM2.5 concentration range for the other rooms was 5-16 pg/m^ with an average of approximately 10 pg/m^. The average ^1^2.5 concentration for the entire school building was approximately 10 pg/mT In addition to higher efficiency rating filters on their HVAC units, portable High Efficiency Particulate Air (HEPA) purifiers were placed in Rooms 327, 333. 638 and 740. The PMn.S concentration range for these rooms w as 5-15 pg/nP with an average of approximately 10 pg/mA

CITY_21MC100_0 03044896

NYC-WTC_000311200

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000311200Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →