* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TVOC Concentralion

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building; • The HEPA air purifiers in rooms 638 and 740 were shut off.

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Concentrations of respirable particulates, CO and TVOCs were within applicable standards and guidelines.

2. Four (4) CO2 measurements were above the range recommended by ASHRAE 62-1999. All others were below the recommended maximum concentration.

3. All indoor measurements of relative humidity were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort.

4. Two (2) temperature measurements were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions).

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this repoil, please call (212) 353-8280, extension 261 or2l2.

Sincerely, ATCASSOCfATES /NC. Reviewed by: »

Andreas C. Andreoii James R. Cohn, CIHTCSP Senior Project Manager Regional Manager Industrial Hygiene Division

Attachment

CITY_21MC100_003044897

NYC-WTC_000311201

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000311201Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →