Mr. Bernard P. Orlan -April 10, 2002
Indoor Air Quality Assessment Page 3
H.S. for Leadership & Public Service (M894) ATC Project No. 15-19125-0290
Real-Time Environmental Measurements
ATC collected one hundred and forty (140) sets of real-time environmental measurements
consisting of one hundred and twenty-eight (128) in the school building and twelve (12)
outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the
Attachment. Readings began at 10:45 A.M. and concluded after 1:50 P,M. The results are
described below.
Temperature
Indoor dry bulb temperature measurements ranged from 70.3 °F to Tl.S °F. One hundred and ten
(110) indoor measurements for temperature were above the range of 68 to 75°F (at 50 percent
relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season
(wintertime conditions). The outdoor temperature range was 68.5 °F to 73.4 °F.
Jielative Humidity
The relative humidity indoors ranged from 42.2 percent to 52.9 percent. All of the indoor
measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60
percent for occupant comfort, The outdoor relative humidity range was 40.9 to 49.2 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 419 ppm to 1410 ppm. Two (2) the indoor
measurements for CO2 were above the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The outdoor (background) CO2
concentration was 422 ppm. Therefore, the maximum acceptable level of CO2 at this location
was 1122 ppm (backgroimd level + 700 ppm). Levels above the recommended maximum do not
indicate a health risk. Carbon dioxide measurements are used as an indicator of available
outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 0 ppm to 2 ppm. These concentrations
were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged
from 2 ppm- 4 ppm.
Respirable Particulates (PM2_5)
Respirable particulate concentrations* indoors ranged between 2 pg/m^ to 36 pg/m^ with an
average 6 pg/m^- All of the indoor measurements for PM2.5 were below the NPAAQS of 65
pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in
aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive
individuals such as asthmatic people and children. The outdoor respirable particulate
concentrations ranged from 36 pg/m^ to 54 pg/m^ with an average of 43 pg/m^. Six (6) of the
twelve (12) instantaneous outdoor measurements were above the USEPA recommended
concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children.
CITY_21MC1OO_OO2918527