NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan April 10, 2002
. Indoor Air Quality Assessment Page 4
H.S. for Leadership & Public Service (M894) ATC Project No. 15-19125-0290
* The measurements made during this assessment were instaritaneous readings, the NPAAQS is
a 24-hour average.
TVOC Concentration
The TVOCs concentrations were 0 ppm inside the building. These concentrations were below
the AJHA guideline for odor control of 1 ppm. The outdoor TVOC concentration was also 0
ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The interior of the building appeared clean and free of dust and debris;
• The building was occupied at the time of the assessment;
• No smoke odor was detected in the building;
FINDINGS
Based on the real-time measurements, the following findings are presented;
1. Concentrations of CO and TVOCs were below applicable standards and guidelines.
2. One hundred and ten (110) indoor measurements for temperature were above the range of
68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992
during the heating season (wintertime conditions).
3. All of the indoor measurements for relative humidity were within the ASHRAE-
recommended range of 30 to 60 percent for occupant comfort.
4. All of the indoor measurements for PM2.5 were below the NPAAQS of 65 gg/m^ 24-hour
average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter
and the USEPA recommended concentration of 40 gg/m^ for sensitive individuals such as
asthmatic people and children. Six (6) of the twelve (12) instantaneous outdoor
measurements were above the USEPA recommended concentration of 40 gg/m^ for
sensitive individuals such as asthmatic people and children.
5. Two (2) CO2 measurements were above the range recommended by ASHRAE 62-1999. All
others were below the maximum concentration.
It is our pleasure to provide these indoor air quality services to the New York City Board of
Education. If you have any questions about this report, please call (212) 353-8280, extension
211or212.
Sincerely, Reviewed by:
J TC ASSOCIA TES INC.
lannis Efstathiou James R. Cohn, CIH, CSP
Senior Project Manager Regional Manager
Industrial Hygiene Division
Attachment
CITY_21MC100_002918528
NYC-WTC_000394737