Indoor air quality report, HS Leadership, Mar 2002

Machine-extracted title · confidence 36%

ATC IAQ measurements at High School for Leadership & [name], 90 Trinity Place, March 25, 2002.

NYC-WTC_000260056–000260059
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan March 26, 2002 Indoor Air Quality Assessment Page 4 H.S. for Leadership & Public Service ('M894) ATC Project No. 15-19125-0290

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TVOC Concentration

The TVOCs concentrations were 0 ppm inside the building. These concentrations were below the AIHA guideline for odor control of 1 ppm. The outdoor TVOC concentration was also 0 ppm.

OBSERVATIDNS

During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building;

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Concentrations, of CO and TVOCs were below applicable standards and guidelines. 2. Seventy (70) indoor measurements for temperature were above and one (1) measurement was below the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). 3. One hundred and twenty-four (124) of the indoor measurements for relative humidity were below the .4SHRAE-recommended range of 30 to 60 percent for occupant comfort. 4. Two (2) of the outdoor measurements for PM2.5 were above the NPAAQS of 65 pg/m^ 24- hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Six (6) of the outdoor measurements were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. 5. Two (2) ol’ the: indoor measurements for CO2 were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level.

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 336 or 212.

Sincerely, Reviewed by: A TC ASSOCIA TES INC.

James R. Cohn, CIH, CSP Senior Project Manager Regional Manager Industrial Hygiene Division

Attachment

CONFIDENTIAL, CITY_21MC100_003463789 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000260059

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000260059Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000394734

Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.

Similar indexed content

NYC-WTC_000260451

Indoor air quality measurements taken May 22, 2002 for BOE.

Similar indexed content

NYC-WTC_000410919

Indoor air quality measurements conducted at the High School for Leadership & [name], June 2002.

Similar indexed content

NYC-WTC_000399254

Indoor air quality report dated May 7, 2002 for High School project; ATC.

Similar indexed content

Compare copies and versions →