Mr. Bernard P. Orlan March 26, 2002 Indoor Air Quality Assessment Page 3 H.S. for Leadership & Public Service (MS94) ATC Project No. 15-19125-0290 Real-Time Environmental Measurements
.ATC collected one hundred and forty (140) sets of real-time environmental measurements consisting of one hundred and twenty-eight (128) in the school building and twelve (12) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings began at 8;06 A.M. and concluded after 2:54 P.M. The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 63.9 °F to 78.1 °F. Seventy (70) indoor measurements for temperature were above and one (1) measurement was below the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature range was 41.7 °F to 49.3 °F.
Relative Humidity
The relative humidity indoors ranged from 20.2 percent to 40.7 percent. One hundred and twenty-four (124) of the indoor measurements for relative humidity were below the ASHRAE- recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 22.4 to 34.0 percent.
Cai'hQiiDioxideConcentratiou
Carbon dioxide concentrations indoors ranged from 357 ppm to 1297 ppm. Two (2) of the indoor measurements for CO2 were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) COo concentration was 436 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1136' ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
CarbonMonond^'Joncentrat^^
Carbon monoxide concentrations indoors ranged from 0 ppm to 2 ppm. These concentrations were below the NP.A.AQS/'ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 2 ppm- 5 ppm.
Respirable Pariiculates
Respirable particulate concentrations* indoors ranged between 4 pg/m^ to 39 pg/m^ with an average 8 pg/m^- None of the indoor measurements for PM2 5 were above the NPAAQS of 65 pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter or above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentrations ranged from 37 pg/m^ to 86 pg/m^ with an average of 49 pg/m^.
CONFIDENTIAL, CITY_21MC100_003463788 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000260058
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000394734
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260451
Indoor air quality measurements taken May 22, 2002 for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410939
Documentation of accreditation scope for bulk asbestos analysis at ATC lab.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410919
Indoor air quality measurements conducted at the High School for Leadership & [name], June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399254
Indoor air quality report dated May 7, 2002 for High School project; ATC.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399272
May 2002 IAQ measurements at High School for Leadership & Space; BOE requested assessment.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394850
ATC IAQ report for High School for Leadership & [name], Trinity Place, April 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260505
ATC IAQ measurement report for High School for Leadership & [name], May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260052
ATC report of IAQ measurements at the referenced school, March 22, 2002, for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410931
IWQ measurements and narrative for H.S. Leadership project, June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410935
ISO/IEC quality systems-related material associated with project records.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000189397
Report of indoor air quality measurements collected at a school on April 9, 2002, to determine if acceptable air quality is maintained.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000260052
ATC report of IAQ measurements at the referenced school, March 22, 2002, for BOE.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000211859
Letter and report from ATC Associates detailing indoor air quality measurements collected at the school on March 25, 2002, to evaluate possible contamination.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394734
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370524
Indoor air quality measurements collected March 20, 2002 at the referenced school.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000296754
ATC memo with IAQ measurements at HS for Leadership & [name], Apr 11, 2002, BOE request.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260108
ATC IAQ measurements collected April 16, 2002 at the referenced school under BOE request.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
Similar indexed content
Indoor air quality measurements taken May 22, 2002 for BOE.
Similar indexed content
NYC-WTC_000410939
Documentation of accreditation scope for bulk asbestos analysis at ATC lab.
Similar indexed content
Indoor air quality measurements conducted at the High School for Leadership & [name], June 2002.
Similar indexed content
Indoor air quality report dated May 7, 2002 for High School project; ATC.
Similar indexed content