NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 4 pages

Indoor air quality report, HS Leadership, Mar 2002

Machine-extracted title · confidence 37%

ATC report of IAQ measurements at the referenced school, March 22, 2002, for BOE.

NYC-WTC_000260052–000260055
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orian March 25, 2002 Indoor Air Quality Assessment Page 3 H.S. for Leadership & Public Service (M894) ATC Project No. 15-19125-0290 Real-Time Environmental Measurements

ATC collected one hundred and twenty-three (123) sets of real-time environmental measurements consisting of one hundred and seventeen (117) in the school building and six (6) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings began at 8:30 A.M. and concluded after 2:42 P.M. The results are described below.

Temperature

Indoor dry bulb temperature measurements ranged from 59.7 °F to 75.8 °F. Seventeen (17) indoor measurement for temperature were above and two (2) measurements were below the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55- 1992 during the heating season (wintertime conditions). The outdoor temperature range was 33.2 °F to 35.0 °F.

Relative Humidity

The relative humidity indoors ranged from 16.2 percent to 36.6 percent. One hundred and fifteen (115) of the indoor measurements for relative humidity were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 22.5 to 24.4 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 358 ppm to 974 ppm. All of the indoor measurements for CO2 were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 327 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1027 ppm (background level -1- 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors ranged from 1 ppm to 2 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 1 ppm- 3 ppm.

Respirable Particulates (PM2_s)

Respirable particulate concentrations* indoors ranged between 1 pg/m^ to 15 pg/m^ with an average 3 pg/rn^- None of the indoor or outdoor measurements for PM2.5 were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter or above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentrations ranged from 15 pg/m^ to 28 pg m- with an average of 20 pg/m3.

CONFIDENTIAL, CITY_21MC100_0 03463771 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000260054

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000260054Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000370553

ATC reports IAQ measurements taken March 22, 2002 at High School for Leadership & [name].

Similar indexed content

NYC-WTC_000399272

May 2002 IAQ measurements at High School for Leadership & Space; BOE requested assessment.

Similar indexed content

NYC-WTC_000399254

Indoor air quality report dated May 7, 2002 for High School project; ATC.

Similar indexed content

Compare copies and versions →