Mr. Bernard P. Orlan March 20, 2002
Indoor Air Quality Assessment Page 3
H.S. for Leadership & Public Service (M894~) ATC Project No. 15-19125-0290
Real-Time Environmental Measurements
ATC collected one hundred and forty (140) sets of real-time environmental measurements
consisting of one hundred and twenty-eight (128) in' the school building and twelve (12)
outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the
Attachment. Readings began at 7:37 A.M. and concluded after 3:03 P.M. The results are
described below.
Temperature
Indoor dry bulb temperature measurements ranged from 69.4 °F to 76.3 °F. One hundred and
twenty-five (125) indoor measurement for temperature were within and three (3) measurements
were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE
Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature
range was 45.3 °F to 46.5 °F.
Relative Humidity
The relative humidity indoors ranged from 28.4 percent to 40.4 percent. Fifty-nine (59) of the
indoor measurements for relative humidity were below and sixty-nine (69) were within the
ASHRAE-recommended range Of 30 to 60 percent for occupant comfort. The outdoor relative
humidity range was 42.7 to 45;8 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 432 ppm to 1003 ppm. All of the indoor
measurements for CO2 were below the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The outdoor (background) CO2
concentration was 511 ppm. Therefore, the maximum acceptable level of CO2 at this location
was 1211 ppm (background level + 700 ppm). Levels above the recommended maximum do not
indicate a health risk. Carbon dioxide measurements are used as an indicator of available.
outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 1 ppm to 2 ppm. These concentrations
were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged
from 1 ppm- 4 ppm.
Respirable Particulates (PM2,s)
Respirable particulate concentrations* indoors ranged between 6 pg/m^ to 22 pg/m^ with an
average 11 pg/m^- All of the indoor measurements for PM2.5 were below the NPAAQS of 65
pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in
aerodynamic diameter and the USEPA recommended concentration for sensitive individuals
such as asthmatic people and children of 40 pg/m^. The outdoor respirable particulate
concentrations ranged from 44 pg/m^ to 121 pg/m^ with an average of 77 pg/m^. Eight (8) of
the outdoor measurements were above the NPAAQS of 65 pg/m3 24-hour average concentration
of particulate matter 2.5 micrometers or less in aerodynamic diameter. All of the twelve (12)