NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan . March 20, 2002
Indoor Air Quality Assessment Page 4
H.S. for Leadership & Public Service (M894) ATC Project No. 15-19125-0290
instantaneous outdoor readings were above the USEPA recommended concentration for
sensitive individuals such as asthmatic people and children of 40 pg/m^.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
TVOC Concentration
The TVOCs concentrations were 0 ppm inside the building. These concentrations were below
the AIHA guideline for odor control of 1 ppm. The outdoor TVOC concentration was also 0
ppm-
OBSERVATIONS
During this assessment, ATC noted the following:
• The interior of the building appeared clean and free of dust and debris;
• The building was occupied at the time of the assessment;
• No smoke odor was detected in the building;
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of CO2, CO, and TVOCs were below applicable standards and guidelines.
2. One hundred and twenty-five (125) indoor measurement for temperature were within and
three (3) measurements were above the range of 68 to 75°F (at 50 percent relative humidity)
recommended by ASHRAE Standard 55-1992 during the heating season (wintertime
conditions).
3. Fifty-nine (59) of the indoor measurements for relative humidity were below and sixty-nine
(69) were within the ASHRAE-recommended range of 30 to 60 percent for occupant
comfort.
4. All of the indoor measurements for PM2.5 were below the NPAAQS of 65 pg/m^ 24-hour
average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter
and the USEPA recommended concentration for sensitive individuals such as asthmatic
people and children of 40 pg/m^. Eight (8) of the outdoor measurements were above the
NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers
or less in aerodynamic diameter. All of the twelve (12) instantaneous outdoor readings were
above the USEPA recommended concentration for sensitive individuals such as asthmatic
people and children of 40 pg/m^.