Mr. Bernard P. Orlan Februars 6. 2002 Indoor Air Quality Assessment Page 3 P. S. 234M ATC Project No. l5-i9125-02?9

Real-Time Environmental Measurements

ATC collected sixty (60) sets of real-time environmental measurements consisting of fifty (50) from inside the school building and ten (10) outdoors. All three floors of the school were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 10:00 A.M. and concluded after 2:55 P.M.

Temperature

Indoor dry bulb temperature measurements ranged from 65.9 °F to 77.7 °F. One (1) measurement was below and one (1) more measurement was above the range of 68 to 75°F (at 50 percent relative humidity) as recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). All other temperature measurements were within the recommended range. The outdoor temperature measurements ranged from 33.2 to 37.9 °F.

Helative HumitJily

The relative humidity indoors ranged from 12.2 percent to 33.8 percent. Only one (1) of the measurements was within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. All other relative humidity measurements were below the ASHR.AE recommended range. The outdoor relative humidity ranged from 10.2 to 13.5 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 613 ppm to 124.3 ppm. Nine (9) COg measurement was above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO? concentration was 475 ppm. Therefore, the maximum acceptable level of COo at this location was 1175 ppm (background level + 700 ppm). The highest measurement was recorded in room 322. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of COo indoors is occupant respiration. The school building was occupied during ATC’s assessment.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors was 0 ppm for all readings. These concentrations were below the 'NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 0 to 1 ppm.

Respirable Fariiculates (PM2,5)

Respirable particulate concentrations* indoors ranged between 6 pg/m^ to 20 pg/m^. Ail measurements were within the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PMoj concentration for the entire school building was approximately 12 pg'mA This average concentration was below the USEPA recommended concentration for sensitive individuals such

CITY_21MC100_002878456

NYC-WTC_000382006

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000382006Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

IAQ report, PS 234M, Feb 2002

NYC-WTC_000382038

ATC indoor air quality report for PS 234M, February 2002, BOE request noted.

Similar indexed content

Compare copies and versions →