Mr. Bernard P. Orlan January 28. 2002 Indoor Air Quality Assessment Page 3 P. S. 89M ATC Project No. 15-19125-0297

Real-Time Environmental Measurements

ATC collected eighty (80) sets of real-time environmental measurements consisting of seventy- two (72) from inside the school building and eight (8) outdoors. All five floors of the school were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 8;00 A.M. and concluded after 2:40 P.M.

Temperature

Indoor dry bulb temperature measurements ranged from 68.0 °F to 73.9 °F. All measurements were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature measurements ranged from 44.8 to 50.9 °F.

Relative Humidity

The relative humidity indoors ranged from 16.8 percent to 29.2 percent. All measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 19.0 to 31.2 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 488 ppm to 1690 ppm. Two (2) CO? measurement was above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations ranged from 448 to 466 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1166 ppm (background level -1- 700 ppm). Tlie highest CO2 reading was found in room 408. At the time of ATC’s assessment, this room was occupied by approximately twenty-eight (28) people. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary' source of CO2 indoors is occupant respiration. The school building during ATC’s assessment was not occupied.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were Oppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 0 ppm.

Respirable Particulates (PM2,5)

Respirable particulate concentrations* indoors ranged between 6 pg/m^ to 28 pg'mY All measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM?.5 concentration for the entire school building was approximately 13 pg'mY This average concentration was well below the USEPA recommended concentration of 40 pg/m^ for sensitive

CITY_21MC1OO_OO2881152 NYC-WTC_000384042

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000384042Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

IAQ report, PS 89M, 2002

NYC-WTC_000383724

Indoor air quality report for PS 89M; measurements taken Feb 2002.

Similar indexed content

Compare copies and versions →