Mr. Bernard P. Orlan March 22. 2002 Indoor Air Quality Assessment Page 3 P. S. 150M ATC Project No. 15-19125-0289
Real-Time Environmental Measurements
ATC collected forty' (40) sets of real-time environmental measurements consisting of thirty (30) from inside the school building and ten (10) from outdoors. All three floors of the school building were surx'eyed. These results are described below.
field data sheets are found in Attachment 1. Readings began at 2:10 P.M. and concluded at approximately 3:35 P.M.
Indoor dry bulb temperature measurements ranged from 69.8°F to 74.8°F. All of the measurements were within the range of 68 to 75°F (at 50 percent relative humidity) as recommended by the .ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature measurements ranged from 51.9 to 54.8°F.
Tne relative humidity indoors ranged from 20.9 to 31.8 percent. Twenty-two (22) of the measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. Tlie outdoor relative humidity measurements ranged from 21.9 to 24.0 percent.
Carbon Dioxide. Concentration
Carbon dioxide concentrations indoors ranged from 409 ppm to 816 p]im. All of the COp measurements were within the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 448 ppm. Therefore, the maximum acceptable level of COg at this location was 1148 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. Ihe school building was occupied during ATC’s assessment.
Carbon Monoxide Concentration
Carbon monoxide concentrations were 0 ppm for the interior readings. Tliese concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 0 ppm for all collected readings.
Respirable .Particulates (PMt,
Respirable particulate concentrations* indoors ranged between 16 pg/m^ to 25 pg/m^. None of the measurements were above the NPAAQS of 65 pg/m-^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PMoty concentration for the entire school building was approximately 20 pg/m^. The PM2,5 average concentration was below the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration measurements ranged from 38 to 48 pg/m^ with an average of 42 pg/m^.
CITY_21MC100_0 02954227
NYC-WTC_000289420
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000249732
ATC indoor air quality measurements report for PS 150M, April 2002.
11 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300714
ATC IAQ measurements at PS 150M in March 2002 for pre-occupancy evaluation.
11 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300833
IAQ field report for PS 150M, March 2002.
11 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253671
IAQ measurements collected at PS 150M for BOE pre-occupancy evaluation.
11 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000214968
Letter from ATC Associates reporting indoor air quality measurements collected at PS 150M on March 27, 2002, prior to re-occupancy.
11 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000289458
ATC memo presenting indoor air quality measurements at PS 150M prior to re-occupancy.
11 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300829
IAQ measurements at PS 150M prior to re-occupancy, March 2002.
11 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300682
ATC reports IAQ measurements at a NYC BOE school before re-occupancy, Feb 2002.
11 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374656
Indoor air quality measurements at P.S. 150M, Greenwich Street, Apr 2002.
11 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375501
ATC IAQ measurements at P.S. 150M before re-occupancy, March 25, 2002.
11 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375441
Indoor air quality measurements at P.S. 150M, school building prior to re-occupancy.
11 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300811
IAQ measurements at PS 150M prior to re-occupancy, March 2002.
11 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000300642
ATC IAQ measurements for PS 150M prior to re-occupancy.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300833
IAQ field report for PS 150M, March 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300829
IAQ measurements at PS 150M prior to re-occupancy, March 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300655
ATC IAQ field report for PS 150M, Feb 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374664
Indoor air quality measurements at P.S. 150M, Greenwich Street, Apr 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300651
ATC indoor air quality evaluation at PS 150M for re-occupancy.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000249732
ATC indoor air quality measurements report for PS 150M, April 2002.
Similar indexed content
NYC-WTC_000300714
ATC IAQ measurements at PS 150M in March 2002 for pre-occupancy evaluation.
Similar indexed content
NYC-WTC_000300833
IAQ field report for PS 150M, March 2002.
Similar indexed content
NYC-WTC_000253671
IAQ measurements collected at PS 150M for BOE pre-occupancy evaluation.
Similar indexed content
NYC-WTC_000214968
Letter from ATC Associates reporting indoor air quality measurements collected at PS 150M on March 27, 2002, prior to re-occupancy.
Similar indexed content