Mr. Bernard P. Ori an May 24,2002
Indoor Air Qualitv' Assessment Page 3
P. S. 234M ATC Project No. 15■■ 19125-0279
R E AI YTm E Environm entai. Measurements
ATC collected sixty (60) sets of real-time environmental measurement.s consisting of fifty-one
(51) from nside the school building and nine (9) outdoors. All three floors of the school were
surveyed, fhesc result.s are described below.
Field data sheets are found in Attachment 1. Reading.s began at 2:00 P.M. and concluded after
4:-)0 P.M.
7’tmnerattijT
Indoor dr}' bulb temperature measurements ranged from 68.6 "F to 75.2 °F. Sixteen (16) indoor
measurements for temperature were below and none of the readings were above the range of 73
to 79°F (at 50 percent relative humidity) as recommended by ASHRAF Standard 55-1992 during
the summer .season. The outdoor lemperature measurements ranged from 66.4 to 68.6 °F.
Relative Hiti.'iiditv
fhe relatixe humidity indoor.s ranged from 29.6 percent to 37.6 percent. Four (4) indoor
measurements for relative humidity were below the ASHRAE-recommended range of 30 to 60
percent for occupant comfort, fhe outdoor relative humidity ranged from 29.5 to 30 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 563 ppm to 917 ppm. All of the
measurements were below the ASHRAF Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level, 'fhe maximum outdoor (background)
Cf)2 concentration was 535 ppm. Therefore, the maximum acceptable level of CO2 at this
location was 1235 ppm (background level + 700 ppm). Levels above the recommended
maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator
of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 1 ppm to 2 ppm. These concentrations
were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were 2
ppm for af readings.
Respirable Particidates (PMt §)
Respirable particulate concentrations* indoors ranged between 20 pg/m^ to 37 pg/m3 with an
average approximately 31 pg/m^- None of the measurements collected indoors for respirable
particulate concentrations were above the NPAAQS 65 pg/m-^ 24-hour average concentration of
particulate matter 2.5 micrometers or less in aerodynamic diameter or above the LISEPA
recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor
respirable particulate concentration ranged from 65 pg/m^ to 70 pg/m^ with an average of
approximately 67 pg/m^.