Mr. Bernard P. Orlan May 24,2002
Indoor Air Quality Assessment Page 4
P. S. 234M ATC Project No. 15 -19125-0279
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
woe Concentration
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The building was occupied at the time of the assessment;
• No smoke odor was detected in the building.
FINDfNGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of indoor respirable particulates, CO2, CO, and TVOCs were below
applicable standards and guidelines.
2. Sixteen (16) indoor measurements for temperature were below and none of the readings w ere
above the range of 73 to 79°F (at 50 percent relative humidity) as recommended by
ASHR.AE Standard 55-1992 during the summer season.
3. Four (4) indoor measurements for relative humidity were below the ASHRAE-recommended
range of 30 to 60 percent for occupant comfort.
It is our pleasure to provide these indoor air quality services to the New York City Board of
Education. If you have any questions about this report, please call (212) 353-8280, extension
211 or212
Sincerely,
ATC ASSOCIATES INC.
Reviewed by:
James R. Cohn, CIH, CSP
Senior Project Manager Regional Manager, Industrial Hygiene Division