Mr. Bernard P. Orlan May 29, 2002 Indoor Air Q'uality Assessment Page 3 P. S. 234M ATC Project No. 15-19125-0279
REAiyriME ENVIROT^ENTAL MEASUREMENTS
ATC collected sixty (60) sets of real-time environmental measurements consisting of fifty-one (51) from inside the school building and nine (9) outdoors. All three floors of the school were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 7:00 AM and concluded after 12:41 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 64.1 °F to 77.1 °F. Eleven (11) indoor measurements for temperature were below and forty (40) of the measurements were within the range of 73 to 79°F (at 50 percent relative humidity) as recommended by ASHRAE Standard 55- 1992 during the summer season. The outdoor temperature measurements ranged from 64 to 64.1°F.
Relative Humidity
The relative humidity indoors ranged from 49.6 percent to 65.1 percent. One (1) of the indoor measurements for relalo'e humidity was above the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 65.1 to 65.2 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 512 ppm to 1028 ppm. All of the measurements were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 523 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1223 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 1 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were 1 ppm for all readings.
Respirable Particulates (PM2,5)
Respirable particulate concentrations* indoors ranged between 6 pg/m^ to 16 pg/m^ with an average approximately 11 pg/m^- None of the measurements collected indoors for respirable particulate concentrations were above the NPAAQS 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration ranged from 5 pg/m^ to 14 pg/m^ with an average of approximately 10 pg/m^.
CITY_21MC1OO_OO2852O43
NYC-WTC_000372059
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000371953
ATC indoor air quality measurements at PS 234M, May 9, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000371997
ATC IAQ measurements at PS 234M, May 16–17, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372007
ATC measurement report for PS 234M indoor air quality requested by BOE, May 17, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000371929
May 2002 IAQ measurement report for PS 234M, BOE.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000371943
Indoor air quality report for PS 234M; measurements collected May 8, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315270
ATC report of indoor air quality measurements at PS 234M; BOE program, May 29, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372129
ATC furnishes IAQ measurement results for PS 234M as part of BOE program.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315123
Indoor air quality measurements collected May 6, 2002 for PS 234M.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372139
ATC IAQ measurements collected at PS 234M for BOE review.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397541
ATC IAQ measurements collected May 28, 2002 for P.S. 234M.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000371895
ATC IAQ measurements collected at P.S. 234M in April 2002.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397355
Indoor air quality measurements recorded April 26, 2002 at PS 234M.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000397399
ATC IAQ measurements at P.S. 234M, requested by BOE, May 2002.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372183
ATC IAQ measurements for PS 234M per BOE program.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397591
ATC IAQ measurements at PS 234M to determine maintenance of acceptable indoor air quality.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397729
ATC IAQ report for PS 234M; summarizes June 25, 2002 measurements.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397719
ATC indoor air quality measurements reported for PS 234M; June 2002.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372119
ATC IAQ measurements at PS 234M for BOE, June 2002.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000371953
ATC indoor air quality measurements at PS 234M, May 9, 2002.
Similar indexed content
NYC-WTC_000371997
ATC IAQ measurements at PS 234M, May 16–17, 2002.
Similar indexed content
NYC-WTC_000372007
ATC measurement report for PS 234M indoor air quality requested by BOE, May 17, 2002.
Similar indexed content
NYC-WTC_000371929
May 2002 IAQ measurement report for PS 234M, BOE.
Similar indexed content
NYC-WTC_000371943
Indoor air quality report for PS 234M; measurements collected May 8, 2002.
Similar indexed content