Mr. Bernard P. Orlan May 3,2002 Indoor Air Quality Assessment Page 3 P. S. 234M ATC Project No. 15-19125-0279
Real-Time Envi^nmental Measurements
ATC collected sixty (60) sets of real-time environmental measurements consisting of fifty-one (51) from inside the school building and nine (9) outdoors. All three floors of the school were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 2:00 P.M. and concluded after 4:15 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 68.3°F to 74.8°F. Sixteen (16) indoor measurements for temperature were below the range of 73 to 79°F (at 50 percent relative humidity) as recommended by ASHRAF Standard 55-1992 during the summer season. The outdoor temperature measurements ranged from 52.5 to 53.6°F.
Relative Humidity
The relative humidity indoors ranged from 38.6 percent to 49.6 percent. All indoor measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 43.6 to 54.0 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 509 ppm to 1199 ppm. One (1) of the measurements was above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 480 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1180 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 0 ppm to 2 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 0 ppm to 1 ppm.
Respirable Particulates (PM2,5)
Respirable particulate concentrations* indoors ranged between 13 pg/m^ to 34 pg/m^ with an average 20 pg/m^- All measurements collected indoors for respirable particulate concentrations were below the NPAAQS 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration ranged from 24 pg/m^ to 50 pg/m^ with an average of 29 pg/m^.
CITY_21MC100_002920419
NYC-WTC_000397401
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000315208
Indoor air quality measurements collected May 17, 2002 at PS 234M.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315182
Indoor air quality measurements collected May 14, 2002 for PS 234M.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315101
Indoor air quality measurements collected May 2, 2002 at PS 234M.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315230
ATC IAQ measurements at PS 234M; BOE program to assess indoor air quality, May 21, 2002.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397509
ATC IAQ measurements collected May 21, 2002 at PS234M for BOE review.
12 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000199225
ATC Associates reports indoor air quality measurements collected at P.S. 234M on June 13, 2002 for the NYC Board of Education.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000371915
ATC indoor air quality measurements for PS 234M requested by NYC BOE, May 2002.
12 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315171
Indoor air quality measurements collected May 13-14, 2002 at PS 234M.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315149
ATC IAQ measurements at PS 234M for BOE program, May 9, 2002.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397499
ATC provides IAQ measurements collected May 20, 2002 for PS234M.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000223944
Cover letter from ATC Associates submitting indoor air quality measurement results for PS 234M collected on May 24, 2002.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000199213
ATC Associates reports indoor air quality measurements collected at P.S. 234M on May 24, 2002 for the NYC Board of Education.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000397465
ATC IAQ measurements at PS234M, May 14, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397591
ATC IAQ measurements at PS 234M to determine maintenance of acceptable indoor air quality.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000212729
Cover letter and report from ATC Associates detailing indoor air quality measurements collected at PS 234M on June 5, 2002, for the New York City Board of Education.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315230
ATC IAQ measurements at PS 234M; BOE program to assess indoor air quality, May 21, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397509
ATC IAQ measurements collected May 21, 2002 at PS234M for BOE review.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372119
ATC IAQ measurements at PS 234M for BOE, June 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000315208
Indoor air quality measurements collected May 17, 2002 at PS 234M.
Similar indexed content
NYC-WTC_000315182
Indoor air quality measurements collected May 14, 2002 for PS 234M.
Similar indexed content
NYC-WTC_000315101
Indoor air quality measurements collected May 2, 2002 at PS 234M.
Similar indexed content
NYC-WTC_000315230
ATC IAQ measurements at PS 234M; BOE program to assess indoor air quality, May 21, 2002.
Similar indexed content
NYC-WTC_000397509
ATC IAQ measurements collected May 21, 2002 at PS234M for BOE review.
Similar indexed content