Mr. Bernard P. Orlan June 6. 2002 Indoor Air Quality Assessment Page 3 P. S. 234M ATC Project No. 15-19125-0279 ATC collected sixty (60) sets of real-time environmental measurements consisting of fifty (50) from inside the school building and ten (10) outdoors. All three floors of the school were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 7:00 AM and concluded after 12:50 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 73.2 °F to 77.1 °F. All of the indoor measurements for temperature were within the range of 73 to 79°F (at 50 percent relative humidity) as recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature measurements ranged from 68.7 °F to 68.9 °F.
Relative Humidity
The relative humidity indoors ranged from 34.6 percent to 62.7 percent. Ten (10) of the indoor measurements for relative humidity were above the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 44.6 percent to 44.8 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 543 ppm to 1143 ppm. All of the indoor measurements were within the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 599 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1299 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors was 1 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations was also 1 ppm for all readings.
Respirable Particulates (PM2 j)
Respirable particulate concentrations* indoors ranged between 8 pg/m^ to 19 pg/m^ with an average approximately 13 pg/m^- None of the measurements collected indoors for respirable particulate concentrations were above the NPAAQS 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration ranged from 31 pg/m^ to 34 pg/m^ with an average of approximately 33 pg/m^.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.
CITY_21MC100_002852109
NYC-WTC_000212731
OCR can misread numbers and units. Confirm readings against the page image before using them.
Related records
Browse subjects →Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
Same-box records
11 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗10 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗11 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗10 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗11 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗11 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗11 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗11 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗11 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗11 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000182883
Report of indoor air quality measurements collected at PS 234M on February 13, 2002, to assess acceptable air quality conditions.
11 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗Filed elsewhere
No available related records indexed in this group.
More like this page
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Others also read
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
Similar indexed content
Similar indexed content
Similar indexed content
Similar indexed content
Similar indexed content