Indoor Air Quality
The lAQ evaluation included collection of seventy-five real-time measurements of temperature,
relative humidity, carbon dioxide (CO2), carbon monoxide (CO), respirable particulates and total
volatile organic compounds (TVOC). Currently, there are no regulatory standards for indoor air
quality in non-industrial buildings, such as residential units. For the real-time data collected,
ATC uses the commonly accepted guidelines cited in the following publications:
• Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-1999), American Society of
Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE);
• Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992);
• Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial
Hygiene Association (AIHA).
PARAMETER TARGET LEVEL AGENCY OR
ORGANIZATION
Carbon Dioxide <700 parts per million (ppm) ASHRAE 62
(COJ
above background level
Carbon Monoxide 9 ppm USEPA NPAAQS (as cited in
(CO) ASHRAE 62)
Respirable Particles 50 micrograms per cubic USEPA NPAAQS (as cited in
(PMw) meter of air (pg/m^) ASHRAE 62)
Temperature Summer; 73-79°F at 50% RH ASHRAE 55
Winter: 68-75°F at 50% RH
Relative Humidity 30 - 60 % ASHRAE 55
Total Volatile
Organic
1 ppm AIHA
Compounds
(TVOC)
USEPA = United States Environmental Protection Agency
NPAAQS = National Primary Ambient-Air Quality Standard
AIHA = American Industrial Hygiene Association
All parameters measured during the lAQ assessment were within recommended guideline
ranges.