Mr. Bernard P. Orlan January 11, 2002 Real-Time Air Monitoring Page 2 P.S. 234 (Manhattan) ATC Project No. 15-19125-0279
The assessments were performed consistent with generally accepted indoor air quality assessment practices. As with all such assessments, there were inherent limitations created by constraints of time, operational and work practice variability, variations in indoor air quality parameters, and sampling and analytical accuracy. The results of the sampling represent conditions found on the dates of the survey and may not represent conditions found at other times. The information presented in this report should be used by the Board of Education as a guide to assess the need for further improvements in current indoor air quality control activities.
EVALUATION CRITERIA
Currently, there are no regulatory standards for indoor air quality in non-industrial buildings, such as offices and schools. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications:
Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-1999), American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992); Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).
Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times. TABLE 1 TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED* . , agency or organization Carbon Dioxide (CO2) <700 parts per million (ppm) ASHRAE 62 above background level Carbon Monoxide (CO) 9 ppm ASHRAE 62 (adopted from USEPA NPAAQS) ________________ _ Respirable Particulates 65 micrograms per cubic meter of USEPA NPAAQS , (PM2,) air (pg/m’) 24 hour average Temperature Summer: 73-79°F at 50% RH ASHRAE 55 Winter: 68-75°F at 50% RH Relative Humidity 30 - 60 % ASHRAE 55 Total Volatile Organic 1 ppm AIHA Compounds (TVOC) Hydrogen Sulfide (H^S) 0.01 ppm (one hour) NYS DEC Sulfur Dioxide (SOJ 0.14 ppm (24-hour average) USEPA NPAAQS Nitrogen Dioxide (NO2) 0.053 ppm (annual average) USEPA NPAAQS 0.05 ppm (lOOug/m’) (annual NYS DEC average) USEPA = United States Environmental Protection Agency * Guidelines for NO are NPAAQS = National Primary Ambient-Air Quality Standard not available. AIHA = American Industrial Hygiene Association NYS DEC = New York State Department of Environmental Conservation
CITY_21MC100_000462202 NYC-WTC_000373507
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000177887
Letter and report detailing real-time indoor air quality monitoring conducted at the school in December.
15 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396218
ATC monitoring report detailing real-time IAQ measurements at PS 234 following BOE request, Dec 8–12, 2001.
15 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000208064
ATC Associates report on real-time air monitoring conducted at P.S. 89M in December 2001 to assess environmental conditions.
13 shared non-person entities · 1 shared topics · similarity 0.990
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000400531
Real-time IAQ report for PS 89M covering Dec 15-16, 2001, by ATC Associates.
13 shared non-person entities · 1 shared topics · similarity 0.990
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000383963
ATC reports real-time air monitoring results conducted December 15–16, 2001 at the referenced school.
13 shared non-person entities · 1 shared topics · similarity 0.989
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000325955
Memo presenting real-time air monitoring results for PS 89M, December 2001.
13 shared non-person entities · 1 shared topics · similarity 0.989
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000400554
IAQ report detailing measurements collected January 15, 2002 at PS 89M.
11 shared non-person entities · 1 shared topics · similarity 0.981
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000400542
IAQ report for PS 89M with January 2002 measurements and BOE involvement.
11 shared non-person entities · 1 shared topics · similarity 0.981
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000383974
ATC IAQ measurements conducted January 11, 2002 at P.S. 89M for NYC BOE.
11 shared non-person entities · 1 shared topics · similarity 0.981
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000212701
Cover letter and report from ATC Associates detailing indoor air quality measurements collected at PS 234M on May 22, 2002, for the New York City Board of Education.
9 shared non-person entities · 1 shared topics · similarity 0.981
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000325964
Indoor air quality measurements at PS 89M, Jan 2002, school environment.
11 shared non-person entities · 1 shared topics · similarity 0.981
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000371828
ATC indoor air quality report for PS 234M; measurements collected in April 2002.
10 shared non-person entities · 1 shared topics · similarity 0.980
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000177887
Letter and report detailing real-time indoor air quality monitoring conducted at the school in December.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396218
ATC monitoring report detailing real-time IAQ measurements at PS 234 following BOE request, Dec 8–12, 2001.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000245343
ATC Associates reports IAQ measurements conducted at the referenced school for the NYC BOE.
Similarity score 0.995 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000245321
ATC Associates reports IAQ measurements at P.S. 89M for NYC BOE, January 2002.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292885
IAQ field report for Stuyvesant High School dated Oct 16, 2001.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410435
IAQ measurements report for PS 150M requested by NYC BOE.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000177887
Letter and report detailing real-time indoor air quality monitoring conducted at the school in December.
Similar indexed content
NYC-WTC_000396218
ATC monitoring report detailing real-time IAQ measurements at PS 234 following BOE request, Dec 8–12, 2001.
Similar indexed content
NYC-WTC_000208064
ATC Associates report on real-time air monitoring conducted at P.S. 89M in December 2001 to assess environmental conditions.
Similar indexed content
NYC-WTC_000400531
Real-time IAQ report for PS 89M covering Dec 15-16, 2001, by ATC Associates.
Similar indexed content
NYC-WTC_000383963
ATC reports real-time air monitoring results conducted December 15–16, 2001 at the referenced school.
Similar indexed content