Ambient air sampling report, Tribeca Tower, Feb 2002

Machine-extracted title · confidence 38%

Summary report of ambient air sampling and visual observations after World Trade Center collapse.

NYC-WTC_000407267–000407275
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Tribeca Tower -105 Duane Street ATC Project No.: 09622-0014 Related Management Company, L.P. February 11, 2002 Page 6

Indoor Air Quality The lAQ evaluation included collection of seventy-five real-time measurements of temperature, relative humidity, carbon dioxide (CO2), carbon monoxide (CO), respirable particulates and total volatile organic compounds (TVOC), Currently, there are no regulatory standards for indoor air quality in non-industrial buildings, such as residential units. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications; • Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-1999), American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); • Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992); • Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).

7AGENCYw»7 ^^NIZATlGf

Carbon Dioxide <700 parts per million (ppm) ASHRAE 62 (CO2) above background level Carbon Monoxide 9 ppm USEPA NPAAQS (as cited in (CO) ASHRAE 62)

Respirable Particles 50 micrograms per cubic USEPA NPAAQS (as cited in (PMw) meter of air (pg/m’) ASHRAE 62)

Temperature Summer; 73-79° F at 50% RH ASHRAE 55 Winter 68-75°F at 50% RH Relative Humidity 30 - 60 % ASHRAE 55 Total Volatile Organic 1 ppm AIHA Compounds (TVOC) USEPA = United States Environmental Protection Agency NPAAQS = National Primary Ambient-Air Quality Standard AIHA = American Industrial Hygiene Association All parameters measured during the lAQ assessment were within recommended guideline ranges.

CITY_21MC100_010173376

NYC-WTC_000407273

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000407273Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

No available related records indexed in this group.

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000365363

Ambient air sampling and visual observations after World Trade Center collapse, Feb 2002.

Similar indexed content

NYC-WTC_000209856

Summary report of ambient air sampling and visual observations conducted at Tribeca Park following the World Trade Center collapse.

Similar indexed content

NYC-WTC_000365779

ATC sampling memo documenting asbestos sampling in hallways and mechanical room, Dec 2001.

Similar indexed content

NYC-WTC_000365799

ATC sampling memo detailing 14 ambient air samples at Tribeca Towers, Jan 2002.

Similar indexed content

Compare copies and versions →