Indoor Air Quality
The IAQ evaluation included collection of seventy-five real-time measurements of temperature,
relative humidity, carbon dioxide (CO2), carbon monoxide (CO), respirable particulates and total
I volatile organic compounds (TVOC). Currently, there are no regulatory standards for indoor air
quality in non-industrial buildings, such as residential units. For the real-time data collected,
ATC uses the commonly accepted guidelines cited in the following publications:
I • Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-1999), American Society of
Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE);
I •
Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992);
Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial
,, Hygiene Association (AIHA).
PARAMETER . TARGET LEVEL AGENCY OR
ORGANIZATION
Carbon Dioxide <700 parts per million (ppm) ASHRAE 62
(CO2)
above background level
Carbon Monoxide 9 ppm USEPA NPAAQS (as cited in
(CO) ASHRAE 62)
Respirable Particles 50 micrograms per cubic USEPA NPAAQS (as cited in
(PM10) meter of air (µg/m3) ASHRAE 62)
Temperature Summer: 73-79°F at 50% RH ASHRAE 55
Winter: 68-75°F at 50% RH
Relative Humidity 30 — 60 % ASHRAE 55
Total Volatile
Organic
1 ppm AIHA
Compounds
(TVOC)
USEPA = United States Environmental Protection Agency
NPAAQS = National Primary Ambient-Air Quality Standard
AIHA = American Industrial Hygiene Association
All parameters measured during the IAQ assessment were within recommended guideline
ranges.