Mr. Bernard P Orlan April 15, 2002
Indoor Air Quality Assessment Page 3
F. S. S9M ATCProiectNo. 15-19125-0297
Real-Time EinvIRONM AL MEASUREMENTS
ATC collected eighty (80) sets of real-time environmental measurements consisting of seventy
(70) from inside the school building and ten (10) from outdoors. All five floors of the school
building were surveyed- These results are described below.
Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded at
approximately 11:30 A.M-
Temperature
hidoor dry bulb temperature measurements ranged from 64.5 °F to 73.1 "T. Ten (10) of the
indoor measurements for temperature were below, and sixty (60) were within the range of 68 to
75'T (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992
during the healing season (wintertime conditions). The outdoor temperature measurements
ranged from 47.6 to 49,5 F
Relative Humidity
The relative humidity indoors ranged from 30.7 to 39.8 percent. AH of the indoor measurements
for relative humidity were within the ASHR.AE-recommended range of 30 to 60 percent for
occupant comfort. The outdoor relative humidity measurements ranged from 47.1 to 51 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 539508 ppm to 1230 ppm. One (1) of the
indoor measurements was above the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The maximum outdoor (background)
CO2 concentration was 485 ppm. Therefore, the maxithum acceptable level of CO2 at this
location was 1185 ppm (background level + 700 ppm). The highest reading was taken in room
506 at 9:00 AM with 23 occupants. Levels above the recommended maximum do not indicate a
health risk. Carbon dioxide measurements are used as an indicator of available outside makeup
aif. The primary' source of CO2 indoors is occupant respiration. The school building was
occupied during ATC’s assessment.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 1-2 ppm. These concentrations were
below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 0 ppm
for all collected readings.
Respirable Particulates (PM3 s)
Respirable particulate concentrations* mdoors ranged between 14 pg/m^ to 40 gg/m^. The
average PM2.5 concentration for the entire school building was approximately 25 pg/m^. All of
the indoor measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration
of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA
recommended concentration of 40 for sensitive individuals and children. The outdoor