Indoor air quality report, PS 89M, Warren St, Apr 2002

Machine-extracted title · confidence 42%

ATC IAQ measurements conducted April 9, 2002 at P.S. 89M for NYC BOE.

NYC-WTC_000328227–000328230
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. OrIan April 10,2002 Indoor Air Quality Assessment Page 3 P. S. 89M ATC Proj ect No. 15 -19125 -0297

Real-Time environmental Measurements

ATC collected eighty (80) sets of real-time environmental measurements consisting of seventy (70) from inside the school building and ten (10) from outdoors. All five floors of the school building were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 7:30 A.M. and concluded at approximately 10:40 A.M.

Temperature-

Indoor dry bulb temperature measurements ranged from 68.9 °F to 72.1 °F. All of the indoor measurements were within the range of 68 to -75°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during- the heating season (wintertime conditions). The outdoor temperature measurements ranged from 64.1 to 64.7 °F.

Relative Humidity

The relative humidity indoors ranged from 39.9 to 46.3 percent. All of the measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 45.1 to 48.7 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 374 ppm to 999 ppm. None of the CO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 428 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1128 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. The school building was occupied during ATC’s assessment.

CaidTonMono^e Concentration

Carbon monoxide concentrations indoors were 1 ppm for all readings.. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was also 1 ppm for all collected readings.

Respirable Particulates (PM2 5)

Respirable particulate concentrations* indoors ranged between 6 pg/m^ to ISpg/m^. All of the measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2.5 concentration for the entire school building was approximately 10 pg/m^. The PM2.5 average concentration was below the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration measurements ranged' from. 10 to 15 pg/m^ with an average of 12 pg/m^.

CITY_21MC100_003271693

NYC-WTC_000328229

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000328229Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

IAQ report for PS 89M, Apr 2002 · Box unavailable

NYC-WTC_000220647

Formal indoor air quality assessment report submitted to the Board of Education regarding measurements taken at PS 89M on April 8, 2002.

14 shared non-person entities · 1 shared topics · similarity 0.998

machine-extracted · confidence unavailable · Check page ↗

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Indoor air quality report, P.S. 89M, Apr 16 2002

NYC-WTC_000202319

Report from ATC Associates detailing indoor air quality measurements collected at a New York City Board of Education school to evaluate building conditions.

Similar indexed content

Compare copies and versions →