Mr. Bernard P. Orlan April 15, 2002
Indoor Air Quality Assessment Page 4
P. S. S9M___________________ _ ___________________ ATC Project No. lj-19125-0297
respirable particulate concentration measurements ranged from 46 10 50 pg/m^ with an average
of 36 gg/mS. All of the outdoor measurements were below the NPAAQS of 65 gg’m3 24-hour
average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. All
of the ten (10) instantaneous outdoor readings were above the USEPA recommended
concentration of 40 pg/m^ for sensitive individuals and children.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hoiir average.
TVOCCo nations
TVOCs were not detected anywhere inside the building (0-0 ppm). The outdoor TVOC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following;
• Tlie school building was occupied at the time of the assessment,
• No smoke odor was detected in the building
• The interior of the building appeared clean and free of dust and debris.
FINDINGS
Based on the real-time measuietnents, the following findings are presented.
1. Concentrations of CO2, CO and TVOCs were below die applicable standards and guidelines.
2. Ten (10) of the indoor measurements for temperature were below, and sixty (60) were within
the range of 6S to 75°F (at SO percent relative humidity) as recommended by the ASHRAE
Standard 55-1992 during the heating season (wintertime conditions).
3. All of the indoor measurements for relative humidity were within the ASIERAE-
recommended range of 30 to 60 percent for occupant comfort.
4. One (1) of the indoor measurements was above the ASHRAE Standard 62-1999
recommended maximum concentration of <700 ppm above the background level. The
maximum outdoor (background) CO2 concentration was 4S5 ppm. Therefore, the maximum
acceptable level of CO2 at this location was 11S5 ppm (background level + 700 ppm). The
highest reading was taken in room 506 at 9:00 AM with 23 occupants. Levels above tlic
recommended maximum do not indicate a health risk. Carbon dioxide measurements are
used as an indicator of available outside makeup air. The primary source of CO2 indoors is
occupant respiration. The school building was occupied during ATC’5 assessment.
5. All of the indoor measurements were btlow the NPAAQS of 65 pg/m3 24-hour average
concentration of particulate matter 2.5 micrometers or less in. aerodynamic diameter and the
USEPA recommended concentration of 40 Jig/m^ for sensitive individuals and children. All
of the outdoor laeasuremcDts were below the NPAAQS of 65 pg/m3 24-hour average
concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. All of
the ten (10) instantaneous outdoor readings were above the USEPA recommended
concentration of 40 pg/m^ for sensitive individuals and children.