ATC @1005/015
05/02/2002 13:52 FAX 212 353 8306
Mr. Bernard P. Orlan May 2,2002
Indoor Air Quality Assessment Page 4
P. S. S9M ATC Project No. 15-19125-0297
measurements ranged from 64 to 70 pg/m^ with an average of 76 pg/ro^. Ten (10) of the outdoor
measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of
particulate matter 2.5 micrometers or less in aerodynamic diameter. All ten (10) of the
instantaneous outdoor measurements were above the USEPA recommended concentration of 40
pg/m^ for sensitive individuals and children.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
TVOC Concentrations
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The school building was occupied at the time of the assessment.
• No smoke odor was detected in the building
• The interior of the building appeared clean and free of dust and debris.
ElkiqtNGS
Based on the real-time measurements, the following findings are presented;
1. Concentrations of CO and TVOCs were below applicable standards and guidelines.
2. Sixty-seven (67) of the indoor measurements for temperature were below and three (3)
measurements were within the range of 73 to 79'’F (at 50 percent relative humidity) as
recommended by the ASHRAE Standard 55-1992 during the summer season .
3. All of the indoor measurements for relative humidity were within the ASHRAE-
recommended range of 30 to 60 percent for occupant comfort.
4. One (1) of the indoor measurements for CO2 was above the ASHRAE Standard 62-1999
recommended maximum concentration of <700 ppm above the background level. The
highest reading (1238 ppm ) was measured in room 404 at 10:30 AM with 31 occupants.
Levels above the recommended maximum do not indicate a health risk. Carbon dioxide
measurements are used as an indicator of available outside makeup air. The primary source
of CO2 indoors is occupant respiration. The school building was occupied during ATC’s
assessment.
5. All of the indoor measurements were below the NPAAQS of 65 pg/m^ 24-hour average
concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Seven
(7) of the seventy (70) instantaneous indoor measmements were above the USEPA
recommended concentration of 40 pg/m^ for sensitive individuals and children. Ten (10) of
the outdoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average
concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. All ten
(10) of the instantaneous outdoor measurements were above the USEPA recommended
concentration of 40 pg/m^ for sensitive individuals and children.
CITY_21MC100_012158271
NYC-WTC_000340722
OCR can misread numbers and units. Confirm readings against the page image before using them.