Mr. Bernard P. Orlan May 2,2002
Indoor Air Quality Assessment Pages
P. S. 89M _____________ _________ _ AICProiectNo^l5:49125-02^
Real-Time envirow.viental measurements
ATC collected eighty (80) sets of real-time environmental measurements consisting of seventy
(70) from inside the school building and ten (10) from outdoors. All five floors of the school
building were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded at
approximately 11:30 A.M.
Indoor dry bulb temperature measurements ranged from 63 ®F to 73.2 "F. Sixty-seven (67) of
the indoor measurements for temperature were below and three (3) measurements were within
the range of 73 to 79’F (at 50 percent relative humidity) as recommended by the ASHRAE
Standard 55-1992 during tlie summer season . The outdoor temperature measurements ranged
ftom58.8“Fto59.8°F.
Relative Humidity
The relative humidity indoors ranged from 32,7 to 42 percent. All of the indoor measurements
for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for
occupant comfort. The outdoor relative humidity measurements ranged from 36 to 39,1 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 539 ppm to 1238 ppm. One (1) of the indoor
measurements for CO2 was above the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The maximum outdoor (background)
CO2 concentration was 530 ppm. Therefore, the maximum acceptable level of CO2 at this
location was 1230 ppm (background level + 700 ppm). The highest reading (1238 ppm ) was
measured in room 404 at 10:30 AM with 31 occupants. Levels above the recommended
maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator
of available outside makeup air. The primary source of CO2 indoors is occupant respiration.
The school building was occupied during ATC’s assessment.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 0 ppm to 1 ppm. These concentrations
were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 3
ppm for all collected readings.
Respirable Particulates (PM2j)
Respirable particulate concentrations* indoors ranged between 3 pg/m^ to 61 ug/m^. The
average PM2.5 concentration for the entire school building was approximately 30 g/m^. All of
the indoor measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration
of particulate matter 2.5 micrometers or less in aerodynamic diameter. Seven (7) of tlie seventy
(70) instantaneous indoor measurements were above the USEPA recommended concentration of
40 pg/m3 for sensitive individuals and children. The outdoor respirable particulate concentration
CITY_21MC100_012158270
NYC-WTC_000340721