NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 2 pages

IAQ Field Report, PS 89M, May 2002

Machine-extracted title · confidence 32%

ATC IAQ field report for PS 89M; measurements and readings.

NYC-WTC_000340609–000340610
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

®004 05/17/2002 12:40 FAX 212 353 8306 ATC

Mr, Bernard P. Orlan May 17,2002 Indoor Air Quality Assessment Page 3 P. S. 89M __________________________ ATCProiectNoJL5J^125-0297 Real-Time Eiwironmental Measurements

ATC collected seventy-nine (79) sets of real-time environmental measurements consisting of seventy (70) from inside the school building and nine (9) from outdoors. All five floors of the school building were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 8:00 A,M. and concluded at approximately 11:30 A-M.

Temverature

Indoor dry bulb temperature measurements ranged from 70.2°F to 75.3 ®F. Twenty-seven (29) of the indoor measurements for temperature were below the range of 73 to 79°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the summer season , The outdoor temperature measurements ranged from 62.7 °F to 64 °F.

Relative Humidity

The relative humidity indoors ranged from 30.2 to 35.7 percent. All of tlie indoor measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 32.8 to 35.1 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 484 ppm to 1150 ppm. One (1) of the indoor measurement for CO2 was above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 447 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1147 ppm (background level + 700 ppm). The highest reading (1150 ppm) was taken in room 402 at 10:30 AM with 35 occupants. Carbon dioxide measurements are used as an indicator of available outside makeup air, 'The primary source of CO2 indoors is occupant respiration. Tire school building was occupied during ATC’s assessment.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors ranged from 1 ppm to 2 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were 2 ppm for all collected readings.

Respirable Fariiculates (PM2,5)

Respirable particulate concentrations* indoors ranged between 7 pg/ra^ to 35 pg/m5. The average PM2 5 concentration for the entire school building was approximately 19 pg/m^. All of the indoor measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration measurements ranged from 47 to 58 pg/m^ with an average of 52 |ug/m3.

CITY_21MC100_009261576

NYC-WTC_000340609

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000340609Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →