Mr. Bernard P. Orlan May 20, 2002
Indoor Air Quality Assessment Page 3
P. S. 89M___________________________ ATC Project No. 15-19125-0297
Real-Time Environmental Measurements
ATC collected seventy-nine (79) sets of real-time environmental measurements consisting of
seventy (70) from inside the school building and nine (9) from outdoors. All five floors of the
school building were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began, at 8:00 A.M. and concluded at
approximately 11:30 A.M.
Temperature
Indoor dry bulb temperature measurements ranged from 71.5°F to 78.5 °F. Two (2) of the
indoor measurements for temperature were below the range of 73, to 79°F (at 50 percent relative
humidity) as recommended by the ASHRAE Standard 55-1992 during the summer season . The
outdoor temperature measurements ranged from 68 °F to 68.7 °F.
Relative Humidity
The relative humidity indoors ranged from 38.2 to 47.6 percent. All of the indoor measurements
for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for
occupant comfort. The outdoor relative humidity measurements ranged from 49 to 50 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 429 ppm to 1290 ppm. Tliree (3) of the
indoor measurement for CO2 were above the ASHRAE Standard 62-1999 recommended
maximum concentration of <700 ppm above the background level. The maximum outdoor
(background) CO2 concentration was 449 ppm. Therefore, the maximum acceptable level of
CO2 at this location was 1149 ppm (background level + 700 ppm). The highest reading (1290
ppm) was taken in room 404 at 10:00 AM with 27 occupants. Carbon dioxide measurements are
used as an indicator of available outside makeup air. The primary source of CO2 indoors is
occupant respiration. The school building was occupied during ATC’s assessment.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 2 ppm for all readings. These concentrations were
below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were 2 ppm
for all collected readings.
Respirable Particulates (PM2,5)
Respirable particulate concentrations* indoors ranged between 10 pg/m^ to 36 pg/m^. The
average PM2.5 concentration for the entire school building was approximately 26 pg/m3. All of
the indoor measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration
of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA
recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor
respirable particulate concentration measurements ranged from 58 to 62 pg/m^ with an average
of 60 p.g/m3.