Mr. Bernard P. Orlan May 20, 2002
Indoor Air Quality Assessment Page 4
P. S. SOM ATC Project No. 15-19125-0297
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
IVOC Concentrations
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The school building was occupied at the time of the assessment.
• No smoke odor was detected in the building
• The interior of the building appeared clean and free of dust and debris.
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of CO and TVOCs were below applicable standards and guidelines.
2. Two (2) of the. indoor measurements for temperature were below the range of 73 to 79°F (at
50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the
summer season.
3. All of the indoor measurements for relative humidity were within the ASHRAE-
recommended range of 30 to 60 percent for occupant comfort.
4. Three (3) of the indoor measurement for CO2 was above the ASHRAE Standard 62-1999
recommended maximum concentration of <700 ppm' above the background level. The
highest reading (129'0 ppm) was taken in room 404 at 10:00 AM with 27 occupants. Carbon
dioxide measurements are used as an indicator of available outside makeup air. The primary
source of COn indoors is occupant respiration. The school building was occupied during
ATC’s assessment.
5. All of the indoor respirable particulate measurements were below the NPAAQS of 65 pg/m3
24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic
diameter and the USEPA recommended concentration of 40 ug/mt’ for sensitive individuals
and children.
It IS our pleasure to provide these indoor air quality services to the New York City Board of
Education. If you have any questions about this report, please call (212) 353-8280, extension
211 or 212.
Sincerely,
.1TCASSOCIA TESINC.
Reviewed bv:
Tam^^R. Cohn, CIS) CSP
Senior Project Manager Regional Manager ,
Industrial Hygiene Division
Attachment
CITY_21MC100_003272061
NYC-WTC_000328376
OCR can misread numbers and units. Confirm readings against the page image before using them.