Mr. Bernard P. Orlan April 23, 2002 Indoor Air Quality Assessment Page 4 P. S. 89M ATC Project No. 15-19125-0297
* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average. IVOC Concentrations TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.
OBSERVATIONS During this assessment, ATC noted the following: • The school building was occupied at the time of the assessment. • No smoke odor was detected in the building • The interior of the building appeared clean and free of dust and debris.
FINDINGS Based on the real-time measurements, the following findings are presented:
1. Concentrations of CO and TVOCs were below applicable standards and guidelines. 2. Sixty-seven (67) of the indoor measurements for temperature were below and three (3) were within the range of 73 to 79°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the summer season . 3. All of the indoor measurements for relative humidity were within the ASHRAE- recommended range of 30 to 60 percent for occupant comfort. 4. One (1) of the indoor measurements for CO2 was above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The highest concentration was detected in room # 402 (1220 ppm) at 10:00 AM with 32 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. The school building was occupied during ATC’s assessment. 5. The average PM2.5 concentration for the entire school building was approximately 13 g/m^. All of the indoor and outdoor measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children.
It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 211 or 212.
Sincerely, ATC ASSOCIATES INC. Reviewed by:
lel W1 James R. Cohn, CIH, CSP Senior Project Manager Regional Manager, Industrial Hygiene Division
Attachment
CITY_21MC100_002886645
NYC-WTC_000392669
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000394453
IAQ measurements collected April 22, 2002 for P.S. 89M.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000199015
Cover letter from ATC Associates submitting indoor air quality measurement results for PS89M collected on May 16, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000210980
Report of indoor air quality measurements conducted at P.S. 89M on May 16, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000369813
IAQ measurements collected at PS 89M for BOE; May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000328373
ATC IAQ measurements collected May 17, 2002 for PS 89M; BOE involvement noted.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000211398
Report detailing indoor air quality measurements collected at P.S. 89M on May 17, 2002 to evaluate building air conditions.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000392756
ATC report detailing indoor air quality measurements at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313685
IAQ measurements at PS 89M for May 17, 2002, per BOE request.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313589
Indoor air quality measurements collected at PS 89M for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000369845
IAQ measurements at P.S. 89M provided to BOE, dated May 22, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000392706
ATC indoor air quality measurements conducted at P.S. 89M for BOE evaluation.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000369114
ATC Associates indoor air quality report for P.S. 89M, May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000394453
IAQ measurements collected April 22, 2002 for P.S. 89M.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000210980
Report of indoor air quality measurements conducted at P.S. 89M on May 16, 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313520
Indoor air quality measurements collected at PS 89M for BOE.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000328298
Indoor air quality measurements collected on April 22, 2002 for PS 89M.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000369290
ATC IAQ measurements collected June 14, 2002 for evaluation.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000199015
Cover letter from ATC Associates submitting indoor air quality measurement results for PS89M collected on May 16, 2002.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000394453
IAQ measurements collected April 22, 2002 for P.S. 89M.
Similar indexed content
Cover letter from ATC Associates submitting indoor air quality measurement results for PS89M collected on May 16, 2002.
Similar indexed content
NYC-WTC_000210980
Report of indoor air quality measurements conducted at P.S. 89M on May 16, 2002.
Similar indexed content
NYC-WTC_000369813
IAQ measurements collected at PS 89M for BOE; May 2002.
Similar indexed content
NYC-WTC_000328373
ATC IAQ measurements collected May 17, 2002 for PS 89M; BOE involvement noted.
Similar indexed content