Mr. Bernard P. Ori an April 15,2002
Indoor Air Quality Assessment Page 2
P. S. 89M_______ ______ ATCProiectNo. 15-19125-0297
presented in this report should be used by the BOE as a guide to assess the need for fortlicr
improvements in current indoor air q,uality control activities.
EVALUATION CRITERIA
Currently, there axe no regulatory standards for indoor air quality in non-industrial buildings,
such as offices and schools. For the real-time data collected, ATC uses the commonly accepted
guidelines cited in the following publications:
Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-1999), American Society of
Heating, Refrigerating, and Air-Conditioning Engineers (ASHKAE);
Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992);
Industrial Hygienists Guide io Indoor Air Quality Investigations (1993), American
Industrial Hygiene Association (AIUA).
Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation.
Meeting one, some, or all of the listed values docs not assure that acceptable indoor air quality
will be aehieved at all times.
TABLEI
TARGET GUTOELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED
<targei
Carbon Dioxide <700 parts per million (ppm) ASHRAE62
(CO2) above background level
Carbon Monoxide 5 ppm ASHRAE $2 (adopted from
(CO) USEPA NPAAQS)
Respirable 65 micrograins per cubic meter USEPA NPAAQS
Particulates of air (pg/tn^) 24-hour average
40 pg/in^ 24-hour average USEPA - Recormnendation for
children / sensitive individuals
Temperature Summer: 73-79’F at 50% RH ASHRAE 55
Winter: 68-75°F at 50% RH
Relative Humidity 30-60% ASHRAE55
Total Volatile
Organic Compounds I ppm AIHA
(TVOC)
USEPA = United States Enyiromnental Piot??tion Agency
NPAAQS = National Primary Ambient-Air Quality Standard
AlHA = American Industrial Hygiene Association