Indoor air quality field report, PS 89M, Feb 2002

Machine-extracted title · confidence 60%

ATC IAQ measurements at PS 89M, Feb 2002.

NYC-WTC_000359852–000359855
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

02/08/2002 14:03 FAX 212 353 8306 ATC I2I004

Mr. Bernard P. Orlan February 8,2002 Indoor Air Quality Assessment Page 3 P. S. 89M__________________ ATC Project No. 15-19125-0297

REAL-TUWE E^VIRONM£NYAL MEASUREMENTS

ATC collected eighty (80) sets of real-time environmental measurements consisting of eight (8) outdoors and thirty-two (32) inside in the morning (A,M.) and the same number of readings in the afternoon (P.M.). All five floors of the school were surveyed. The field data sheets are found in the Attachment. Readings began at 8:05 A.M. and concluded after 4:00 P.M. The results are described below;

Tempei'atiff's

Indoor dry bulb temperature rneasurements ranged from 63.5°F to 753°F (A.M.) and 66.9°F to 73.0°F (PM). In the morning, two (2) measurements were above and six (6) were below the range of 68 to 75^F (at 50 percent relative humidity) recommended by ASHRAE Standard 55- 1992 during the heating season (wintertime conditions) while in tlie afternoon seven (7) measurements were below the same recommended range. The average outdoor temperature was 39.7”? (A.M.) and 52.9"F (P.M.).

Relative Humidity

The relative humidity indoors ranged from 15,4 to 25.4 percent (A.M.) and 26.5 to 37.1 percent (P.M.). Fifteen (15) measurements collected in the afternoon were within the AShlRAE- recommended range of 30 to 60 percent for occupant comfort. All other readings were below the recommended range. The outdoor relative humidity averaged 42.3 percent (A.M.) and 36.0 percent (P.M.).

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 520 to 1019 ppm (A.M.) and 535 to 999 ppm (P.M.). All CO2 measurements collected were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above tlie background level. The outdoor (background) CO2 concentrations averaged 494 ppm (A.M.) and 537 ppm (P.M.). Therefore, the maximum acceptable level of CO? at this location was 1237 ppm (background level + 700 ppm). The highest indoor level was measured in Classroom 504. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors i.s occupant respiration. The 2nd and 3rd floors of the school building were not occupied during ATC’s assessment.

Carbon Monoxide Concentratiori

Carbon monoxide concentrations indoors ranged from 0 to 1 ppm. These concenirations were below the ASI-LRAE giiideiine of 9 ppm- The outdoor CO concentration was 0 ppm.

Repairable Pariiculates (RM2_si

Respirable particulate concentrations* indoors ranged from 2) pg/m^ to 42 pg/m^ (A.M.) and 30 |-Lg/m3 to 78 pg/m^ (P.M.). Six indoor measurements collected in the afternoon were above the NPAAQS of 65 ug/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2.5 concentration* for the entire school

CITY_21MC1OO_OO9253154

NYC-WTC_000359854

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000359854Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →