02/07/2002 12,46 FAX 212 353 8306 ATC ®004/014

Mr. Bernard P- Orlan February 7, 2002 Indoor Air Quality Assessment Page 3 P. S. 89M___________ ATCProiectNo. 15-19125-0297

REAL-TTME ENVJROMMEWTAL MEASXIRJSMENTS

ATC collected eighty (80) sets of real-time environmental measurements consisting of eight (8) outdoors and thirty-two (32) inside in the morning (A-M.) and the same number of readings in the afternoon (P.M.). All five floors of the school were suiveyed. The field data sheets are found in the Attachment. Readings began at 8:10 A.M. and concluded after 3:30 P.M. Tlie results are described below:

i ( Temperature

Indoor dry bulb temperature measurements ranged from 68.4'? to 74.4°F (A.M.) and 67.9'T' to TS-S’F (PM). Only one (1) measurement in the afternoon was below the range of 68 to VST (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The average outdoor temperature was 36.0°f (A-M.) and 44.0°F (P.M.).

JieJative Humidity

The relative humidity indoors ranged from 12.2 to 32.0 percent (A.M.) and 13,5 to 18.8 percent (P.M-), Only two (2) readings collected in the moming were within the ASHRAE- rccommended range of 30 to 60 percent for occupant comfort. All other readings were below the recommended range. The outdoor relative humidity averaged 26.0 percent (A,M.) and 30.0 percent (P.M.).

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 478 to 1004 ppm (A.M.) and 479 to 930 ppm (P.M.). All CO2 measurements collected were below the ASHRAE Standard 62-199.9 leconiTncnded maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations averaged 492 ppm (A.M.) and 458 ppm (P.M.). Therefore, the maximum acceptable level of CO2 at this location was 1192 ppm (background level + 700 ppm). The highest indoor level was measured in Classroom 402. Levels above tlte recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available ourdoor air. The primary source of CO2 indoors is occupant respiration. The and 3''^ fioors of the school building were not occupied during ATC’s assessment.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations were below the ASHRAE guideline of 9 ppm. The outdoor CO concentration was also 0 ppm.

Jiespirabie .Pariicuiates

Respirable particulate concentrations* indoors ranged from 11 gg/m^ to 34 (A.M.) and 17 ng/m^ to 30 (ig/iu^ (P.M,). All indoor measurements were below the MPAAQS of 65 p-g/ra^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2.5 concentraiion* for the entire school building was approximarely 24 pg/TO^ (A.M.) and 23 pg/m^ (P.M ). All A.M. and P. M. indoor ineasurCTnents were also

CITY_21MC100_011251387 NYC-WTC_000359842

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000359842Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →