02/07/2002 12:45 FAX212 3538306 ATC @003/014

Mr. Bernard P. Orlan February 7,2002 Indoor Air Quality Assessment Page 2 P. 5. 89M__________________ ATC Project No. 15-19)25-0297

The assessment was performed congi.stent with generally accepted indoor air quality assessment practices. As with all such assessments, there wore inherent limitations created by constraints of time, operational and work practice variability, variations in indoor air quality parameters and sampling and analytical accuracy. The results of the sampling represent conditions found on the dates of the survey and may not represent conditions found at other times. The information presented in this report should be used by the BOE as a guide to assess the need for further improvements in current indoor air quality control activities-

EVALUATION CRITERIA

Currently, there are no regulatory standards for indoor air quality in non-industrial buildings, such as offices and schools. For tire real-time data collected, ATC uses the commonly accepted guidelines died in the following publications;

Vemilation fur Acceptable JrrdoofAir Quality (ASHIfAE 62-1999), American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); Thermal Etiy iron mental Conditions for Human Occupancy (ASHRAE 55-1992): Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA),

Table 1 lists target guidelines for the parameters tliat ATC evaluated during this investigation. Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times.

TABLEI TARGET GUIDELINES TOR INDOOR AIR QUALITY PARAMETERS EVALUATED

Carbon Dioxide <700 parts per million (ppm) ASHRAE 62 (CO2) above background level Carbon Monoxide 9 ppm ASHRAE 62 (adopted from (CO) USEPA NPAAQS) 65 micrograms per cubic meter USEPA NPAAQS Respirable of air (jug/m^) 24-liour average Parliculates (PM2.5) 40 pg/m^ 24-hour average USEPA - recommendation for childrcn/sensitive individuals Temperature Summer; 73-79’^ at 50% RH ASHRAE 55 Winter; 68-75°F at 50% RH Relative Humidity 30-60% ASHRAE 55 Total Volatile Organic Compounds 1 ppm AIHA (TVOC) USEPA = United States Environmental Protection Agency MPAAQS = National Primary Am bi ant-Air Quality Standard AIHA = American Industrial Hygiene Association

CITY_21MC1OO_O11251386 NYC-\/VTC_000359841

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000359841Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →