NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan .lanuary 18, 2002
3 Indoor Air Quality Assessment Page 2
P. S. 89 (Manhattan) ATC Project No. 15-19 l 25-0297
The assessment was performed consistent with generally accepted indoor air quality assessment
practices. As with all such assessments, there were inherent limitations created by constraints of
time, operational and work practice variability, variations in indoor air quality parameters and
sampling and analytical accuracy. The results of the sampling represent conditions found on the
dates of the survey and may not represent conditions found at other times. The information
presented in this report should be used by the BOE as a guide to assess the need for further
improvements in current indoor air quality control activities.
EVALUATION CRITERIA
Currently, there are no regulatory standards for indoor air quality in non-industrial buildings,
such as offices and schools. For the real-time data collected, ATC uses the commonly accepted
guidelines cited in the following publications:
Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-1999}, American Society of
Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE);
Thermal Environmental Conditions for Human Occupancy (ASHRAE 65-1992);
Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American
Industrial Hygiene Association (AIHA).
Table I lists target guidelines for the parameters that ATC evaluated during this investigation.
Meeting one, some, or all of tire listed values does not assure that acceptable indoor air qualify
will he achieved at all times.
TABLE!
TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED
IMRkMlflilR
_________________
ill
T\i«a:ii,r.\i;L AGENCY OR
ORG-XM/.VIION ____________
Carbon Dioxide <700 parts per million (ppm) ASHRAE 62
(CO2) above background level
Carbon Monoxide 9 ppm ASHRAE 62 (adopted from
(CO) USEPA NPAAQS)
Respirable 65 micrograms per cubic meter USEPA NPAAQS
Particulates (PM2 5) of air (fig/m^) 24-hour average
Temperature Summer: 73-79°F at 50% RH ASHRAE 55
Winter: 68-75% at 50% RH
Relative Humidity 30 - 60 % ASHRAE 55
Total Volatile
Organic Compounds 1 ppm Al HA
(TVOC)
USEPA = United States Environmental Protection Agency
NPAAQS ='National Primary Ambient-Air Quality Standard
AIHA = American Industrial Hygiene Association
CONFIDENTIAL, SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008 CITY_21 MC100_014659973
NYC-WTC_000236968
OCR can misread numbers and units. Confirm readings against the page image before using them.