Mr. Bernard P. Orlan February 7, 2002
Indoor Air Quality Assessment Page 3
P. S. 89M___________________ ATC ProjectNo. 15-19125-0297
Real-Time Environmental Measurements
ATC collected eighty (80) sets of real-time environmental measurements consisting of eight (8)
outdoors and thirty-two (32) inside in the morning (A.M.) and the same number of readings in
the afternoon (P.M.). All five floors of the school were surveyed. The field data sheets are
found in the Attachment. Readings began at 8:10 A.M. and concluded after 3:30 P.M. The
results are described below:
Temperature
Indoor dry bulb temperature measurements ranged from 68.4°F to 74.4°F (A.M.) and 67.9°F to
72.8°F (PM). Only one (1) measurement in the afternoon was below the range of 68 to 75°F (at
50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating
season (wintertime conditions). The average outdoor temperature was 36.0°F (A.M.) and 44.0°F
(P.M.).
Relative Humidity
The relative humidity indoors ranged from 12.2 to 32.0 percent (A.M.) and 13.5 to 18.8 percent
(P.M.). Only two (2) readings collected in the morning were within the ASHRAE-
recommended range of 30 to 60 percent for occupant comfort. All other readings were below the
recommended range. The outdoor relative humidity averaged 26.0 percent (A.M.) and 30.0
percent (P.M.).
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 478 to 1004 ppm (A.M.) and 479 to 930 ppm
(P.M.). All CO2 measurements collected were below the ASHRAE Standard 62-1999
recommended maximum concentration of <700 ppm above the background level. The outdoor
(background) CO2 concentrations averaged 492 ppm (A.M.) and 458 ppm (P.M.). Therefore, the
maximum acceptable level of CO2 at this location was 1192 ppm (background level + 700 ppm).
The highest indoor level was measured in Classroom 402. Levels above the recommended
maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator
of available outdoor air. The primary source of CO2 indoors is occupant respiration. The 2'''^
and 3rd floors of the school building were not occupied during ATC’s assessment.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations
were below the ASHRAE guideline of 9 ppm. The outdoor CO concentration was also 0 ppm.
Respirable Particulates ('PM2,5)
Respirable particulate concentrations* indoors ranged from 11 pg/m^ to 34 pg/m^ (A.M.) and
17 pg/m3 to 30 pg/m3 (P.M.). All indoor measurements were below the NPAAQS of 65 pg/m3
24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic
diameter. The average PM2.5 concentration* for the entire school building was approximately
24 pg/m3 (A.M.) and 23 pg/m^ (P.M.). All A.M. and P. M. indoor measurements were also