Mr. Bernard P- Or Ian February 1,2002
Indoor Air Quality Assessment Page 4
P. S. 89M__________________ ATC Project No. 15-19125-0297
below the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as
a.sthmatic people and children. The outdoor respirable particulate concentration averaged 49
(.ig/m^ (A-M.) and 42 p-g/ra^ (P.M.),
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
TVOC Concantration
TVOCs were not deiecied (0.0 ppm) anywhere inside or outside tlie building.
OBSERVATIONS
During this assessment, ATC noted the following:
• The interior of the building appeared clean and free of dust and debris;
• The school was partially occupied (T.S. 89) at the time of the assessment;
• No smoke odor was detected in rhe building.
FINDINGS
Based on the real-time measurements, the following findings are presented;
J. Respirable particulate, CO2, CO and TVOC concentrations were within applicable
guidelines;
2. One (1) mea-surements of temperature in the afternoon was below the recommended range;
3. Two (2) indoor measurements of relative humidity in the morning were within the ASHRAE
recommended range of 30 to 60 percent for occupant comfort. All other measurements were
below the recommended range.
It is our pleasure to provide these indoor air quality services to the New York City Board of
Education. If you have any questions about this report, please call (212) 353-8280, extension
261 or212.
Sincerely, Reviewed by:
J rCASSOClAT£S INC.
Andreas C, Andreou James R. Cohn, CIH, CSP
Senior Project Manager Regional Manager
Industrial Hygiene Division
Attachment