NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 4 pages

Letter: IAQ Report for PS 89M, May 2002

Machine-extracted title · confidence 32%

ATC May 7, 2002 letter to BOE regarding IAQ measurements at PS 89M.

NYC-WTC_000340679–000340682
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

05/07/2002 12:59 FAX 212 353 8306 ATC ®005/014

Mr. Bernard P. Orlan May 7,2002 Indoor Air Quality Assessment Paged P. S.89M ATC Project No. 15-19125-0297 respirable particulate concentration measurements ranged from 88 to 96 (ig/m^ with an average of 92 pg/m^.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TVOC Concentrations

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following; * The school building was occupied at the time of the assessment. • No smoke odor was detected in the building • The interior of the building appeared clean and free of dust and debris.

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Concentrations of CO2, CO and TVOCs were below applicable standards and guidelines. 2. Twenty -three(23) of the indoor measurements for temperature were below the range of 73 to 79°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the summer 3. All indoor measurements for relative humidity were within the ASHRAE-rccomniended range of 30 to 60 percent for occupant comfort. 4. All of the indoor measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 |4.g/m3 for sensitive individuals and children.

It is our pleasure to provide tliese indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 211 or 290.

Sincerely, ATC ASSOCIATES INC Reviewed by:

Prasad Doddapanerfi James R- Cohn, CHI, CSP Senior Project Manager Regional Manager, Industrial Hygiene Division

Attachment

CITY_21MC1OO_O12158257 NYC-WTC_000340682

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000340682Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

IAQ report for PS 89M, May 2002 · page 4

NYC-WTC_000220672

Formal indoor air quality assessment report submitted to the Board of Education regarding measurements taken at PS 89M on May 6, 2002.

Similarity score 0.997 (not a probability)

machine-extracted · confidence unavailable · Check page ↗

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

IAQ report, March 6, 2002

NYC-WTC_000360242

ATC memo transmitting IAQ measurements for PS 89M, March 6, 2002.

Similar indexed content

Compare copies and versions →