&^d07/2002 12:59 FAX 212 353 8306 ATC 121004/014

Mr. Bernard P. Orlan May 7,2002 Indoor Air Quality Assessment Pages P. S. 89M________________ ATC Project No. 15-19125-0297

Real-time Environmental Measmiements ATC collected eighty (SO) sets of real-time environmental measurements consisting of sixty nine (69) from inside the school building and eleven (11) from outdoors. All five floors of the school building were surveyed. These results are described below.

Fjeld data sheets are found in Attachment 1, Readings began at 8:00 A,M, and concluded at approximately 11:30 A.M,

Temperaiure

Indoor dry bulb temperature measurements ranged from 69.5 °F to 75.0 “F. Twenty -three(23) of the indoor measurements for temperature were below the range of 73 to 79’F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the summer season. The outdoor temperature measurements ranged from 58.1°F to 65.3 “F.

Reiative Humidity

The relative humidity indoors ranged from 36-3 to 45.2 percent. All indoor measurements for relative humidity were within the ASHRAE-reconunended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 44.4 to 57.5 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 554 ppm to 979 ppxn. All indoor measurements for CO2 were within the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 550 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1250 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. The school building was occupied during ATC’s assessment.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 1 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration were also 2 ppm for all collected readings.

Respirable Particulates (PM^.s)

Respirable particulate concentrations* indoors ranged between 15 pg/m^ to 42 pg/m^. The average PM2,5 concentration for the entire school building was approximately 30g/m3. All of the indoor measurements were below the NPAAQS of 65 p-g/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 jxg/m^ for sensitive individuals and children. The outdoor

CITY_21MC1OO_O12158256 NYC-WTC_000340681

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000340681Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

IAQ report, March 6, 2002

NYC-WTC_000360242

ATC memo transmitting IAQ measurements for PS 89M, March 6, 2002.

Similar indexed content

Compare copies and versions →